Background Image
Table of Contents Table of Contents
Previous Page  70 / 408 Next Page
Information
Show Menu
Previous Page 70 / 408 Next Page
Page Background

3/20

Technical

Section 11

Dimensions

Section 12

3

Electrical auxiliaries for iC120, DPN,

DPNVigi, ID, C60H-DC, SW60-DC,

C60PV-DC, C60NA-DCdevices

Protection

Circuit protection

Earth leakage protection

Tripping

Auxiliaries

MN

MNs

MNx

Type

Undervoltage release

Instantaneous

Delayed

Independent of the supply voltage

Function

b

b

Causes the device with which it is associated to trip when its input voltage

decreases

(between 70 % and 35 % of Un). Prevents the device from closing until its input

voltage has been restored

b

b

Tripping of the associated device by opening

of the control circuit

(e.g. push-button, dry contact)

b

b

No tripping in the event of

transient voltage dips (up to 0.2 s)

b

b

A drop in the supply voltage does not trip the

associated device

b

b

A locking push-button control allows the

circuit protected (e.g. machine control) to be

placed in safety configuration

Wiring diagrams

U <

E2 N/

L1

L2

E1

Utilization

b

b

Emergency stop via a normally-closed pushbutton

b

b

Ensures the safety of the power supply circuits of several machines by

preventing accidental startups

b

b

Fail-safe emergency stop

b

b

Insensitive to the variation in the control

circuit voltage to improve continuity of service

Important: Before any servicing operation

switch off the mains power supply (voltage

presence at terminals E1/E2)

Catalogue numbers

A9N26960 A9N26961 A9N26959 A9N26963

A9N26969 A9N26971

iC120, DPN, DPN Vigi, ID

b

b

b

b

b

b

b

b

b

b

b

b

C60H-DC, SW60-DC,

C60PV-DC, C60NA-DC

b

b

b

b

b

b

b

b

b

b

b

b

Technical specifications

Rated voltage (Ue) V AC

220…240 48

115

220…240

230

400

V DC

48

Standardised operating and

non-response to voltage times

(Ua)*

Maximum operating time

Minimum non-response time –

Operating

frequency

Hz

50/60

400

50/60

50/60

Mechanical state indicator light,

red

On front face

On front face

On front face

Test function

Width in 9 mm modules

2

2

2

Operating current

Number of contacts

Operating

temperature

°C

-25…+50

-25…+50

-25…+50

Storage

temperature

°C

-40…+85

-40…+85

-40…+85

Standards

IEC/EN 60947-1

b

b

b

b

b

b

IEC/EN 60947-5-1

EN 60947-2

b

b

b

b

EN 62019-2

(1)

(1) For iC120, DPN.

*(Ua): Voltages measured between the phase and the neutral conductor, at which the MSU device must control the associated protective device.

DB118804

DB118805

PB107151-30

PB107152-30

PB107149-30