Background Image
Table of Contents Table of Contents
Previous Page  58 / 408 Next Page
Information
Show Menu
Previous Page 58 / 408 Next Page
Page Background

3/8

Technical

Section 11

Dimensions

Section 12

3

iC120H circuit breakers are multistandard circuit breakers that combine the

following functions:

b

b

circuit protection against short-circuit currents

b

b

circuit protection against overload currents

b

b

suitability for isolation in the industrial sector to IEC/EN 60947-2

b

b

fault tripping and indication by adding auxiliaries.

IEC/EN 60898-1, IEC 60947-2

Catalogue numbers

iC120H circuit breaker

Type

1P

2P

1

2

31

42

Rating (In)

Curve

Curve

B

C

D

B

C

D

63 A

A9N18401

A9N18445

A9N18489

A9N18412

A9N18456

A9N18500

80 A

A9N18402

A9N18446

A9N18490

A9N18413

A9N18457

A9N18501

100 A

A9N18403

A9N18447

A9N18491

A9N18414

A9N18458

A9N18502

125 A

A9N18404

A9N18448

A9N18492

A9N18415

A9N18459

A9N18503

Width in 9 mm modules

3

6

Alternating current (AC) 50/60 Hz

Breaking capacity (Icu) to IEC/EN 60947-2

Service

breaking

capacity (Ics)

Type

Voltage (V)

1P

12 to 130 V 220 to 240 V 380 to 415 V 440 V

Rating (In)

63 to 125 A 30 kA

15 kA

4,5 kA

(1)

-

50 % of Icu

2P, 3P, 4P

12 to 130 V 220 to 240 V 380 to 415 V 440 V

63 to 125 A -

30 kA

15 kA

10 kA 50 % of Icu

Breaking capacity (Icn) to IEC/EN 60898-1

Type

Voltage (V)

1P, 2P, 3P, 4P

230 to 400 V

Rating (In)

63 to 125 A 15000 A

50 % of Icn

(1)

One-pole breaking capacity in IT isolated neutral system (double fault).

Direct current (DC)

Breaking capacity (Icu) according to IEC/EN 60947-2

Service

breaking

capacity (Ics)

Voltage (Ue)

Between +/-

12 to 125 V

y

144 V

y

250 V

y

375 V

y

500 V

Number of poles 1P

2P

3P

4P

Rating (In)

63 to

125 A

20 kA 15 kA 15 kA 15 kA 15 kA 100 % of Icu

PB107913-30

PB107919-30

PB107922-30

PB107916-30

iC120H circuit breakers

(curves B, C, D)

Protection

Circuit protection

Note:

For current ratings below 63 amp use IC60H