Background Image
Table of Contents Table of Contents
Previous Page  60 / 408 Next Page
Information
Show Menu
Previous Page 60 / 408 Next Page
Page Background

3/10

Technical

Section 11

Dimensions

Section 12

3

iC120H circuit breakers

(curves B, C, D) (cont.)

Protection

Circuit protection

Weight (g)

Circuit breaker

Type

iC120H

1P

205

2P

410

3P

615

4P

820

Dimensions (mm)

DB406006

108

9

18

86

81

45

81

54

27 1P

2P

3P

4P

5.5

70

44 16

Connection

Without access. With accessories

DB126143

PZ2

15 mm

6.5 mm

Rating Tightening

torque

Copper cables

50 mm²

Al term.

Screw-on

connection

for ring

terminal

(1)

Multi-cable terminal

Rigid

Flexible or

with ferrule

Rigid

cables

Flexible

cables

63 to 125 A

3.5 N.m 1 to 50 mm

2

1.5 to 35 mm

2

16 to 50 mm

2

Ø 5 mm

3 x 16 mm²

3 x 10 mm²

(1)

For lugs up to 63 A, front or rear accessories.

IP20

IP40

Clips onto 35 mm DIN rail.

Any installation position.

Technical data

Main characteristics

To IEC/EN 60947-2

Insulation voltage (Ui)

500 V AC

Degree of pollution

3

Rated impulse withstand voltage (Uimp)

6 kV

Thermal tripping

Reference temperature 50°C

To IEC/EN 60898-1

Magnetic tripping Curve B

3 and 5 In

Curve C

5 and 10 In

Curve D

10 and 14 In

Limitation class

3

Additional characteristics

Degree of protection

(IEC 60529)

Device only

IP20

Device in a modular

enclosure

IP40 (IPXXD)

Endurance (O-C)

Electrical

63 A

10000 cycles (O-C)

80...125 A 5000 cycles (O-C)

Mechanical

20000 cycles

Operating temperature

-30°C to +70°C

Storage temperature

-40°C to +80°C

Tropicalisation (IEC 60068-1)

Treatment 2 (relative humidity 95% at 55°C)

DB118767

DB122831

DB122945

DB122946

DB122935

DB118789

DB118787

DB122932