3
3/3
i
DPN circuit breakers (cont.)
Protection
Circuit protection
Technical
Section 11
Dimensions
Section 12
DB123310
DB123312
Clip on DIN rail 35 mm.
Indifferent position of installation.
DB123314
IP20
IP40
Weight (g)
Circuit breaker
Type
i
DPN
1P+N
115
Dimensions (mm)
DB406072
4.5
4.5
5.5
18
54
36
3P+N
3P
1P+N
44
78
45
81
Technical data
Main characteristics
i
DPN N
Insulation voltage (Ui)
Phase-to-neutral
400 V
Phase-to-phase
440 V
Voltage rating (Ue)
Phase-to-neutral
230 V
Phase-to-phase
400 V
Magnetic tripping
B curve 3 to 5 In
b
b
C curve 5 to 10 In
b
b
D curve 10 to 14 In
b
b
According to IEC/EN 60898-1
Limitation class
3
Rated breaking capacity (Icn)
6000 A
Service breaking capacity (Ics)
100 % Icn
Rated breaking and making capacity on a single pole (Icn1) Icn1 = Icn
According to IEC 60947-2
Rated impulse withstand voltage (Uimp)
4 kV
Breaking capacity (Icu)
10 kA
Service breaking capacity (Ics)
75 % Icu
Pollution degree
3
Additional characteristics
Degree of protection
(IEC 60529)
Device only
IP20
Device in modular enclosure IP40
Endurance (O-C)
Electrical
y
20 A
20000 cycles
u
25 A
10000 cycles
Mechanical
20000 cycles
Operating temperature
-25°C to +70°C
Storage temperature
-40°C to +70°C
Tropicalization (IEC 60068-1)
Treatment 2 (relative humidity of
95 % at 55°C)
Neutral opening and closing shifted relative to phases
No surge upon operation of the
device