Background Image
Table of Contents Table of Contents
Previous Page  53 / 408 Next Page
Information
Show Menu
Previous Page 53 / 408 Next Page
Page Background

3

3/3

i

DPN circuit breakers (cont.)

Protection

Circuit protection

Technical

Section 11

Dimensions

Section 12

DB123310

DB123312

Clip on DIN rail 35 mm.

Indifferent position of installation.

DB123314

IP20

IP40

Weight (g)

Circuit breaker

Type

i

DPN

1P+N

115

Dimensions (mm)

DB406072

4.5

4.5

5.5

18

54

36

3P+N

3P

1P+N

44

78

45

81

Technical data

Main characteristics

i

DPN N

Insulation voltage (Ui)

Phase-to-neutral

400 V

Phase-to-phase

440 V

Voltage rating (Ue)

Phase-to-neutral

230 V

Phase-to-phase

400 V

Magnetic tripping

B curve 3 to 5 In

b

b

C curve 5 to 10 In

b

b

D curve 10 to 14 In

b

b

According to IEC/EN 60898-1

Limitation class

3

Rated breaking capacity (Icn)

6000 A

Service breaking capacity (Ics)

100 % Icn

Rated breaking and making capacity on a single pole (Icn1) Icn1 = Icn

According to IEC 60947-2

Rated impulse withstand voltage (Uimp)

4 kV

Breaking capacity (Icu)

10 kA

Service breaking capacity (Ics)

75 % Icu

Pollution degree

3

Additional characteristics

Degree of protection

(IEC 60529)

Device only

IP20

Device in modular enclosure IP40

Endurance (O-C)

Electrical

y

20 A

20000 cycles

u

25 A

10000 cycles

Mechanical

20000 cycles

Operating temperature

-25°C to +70°C

Storage temperature

-40°C to +70°C

Tropicalization (IEC 60068-1)

Treatment 2 (relative humidity of

95 % at 55°C)

Neutral opening and closing shifted relative to phases

No surge upon operation of the

device