Background Image
Table of Contents Table of Contents
Previous Page  316 / 408 Next Page
Information
Show Menu
Previous Page 316 / 408 Next Page
Page Background

11

11/2

Dimensions

Section 12

Dissipated power, impedance and

voltage drop

Technical advice

Rating (A)

0.5 1 1.6 2 2.5 3 4 6 6.3 10 12.5 13 16 20 25 32 40 50 63 80 100 125

Circuit breakers

iC60

2.3 2.3

1.9

2.2 2.4 1.3

2

2 2.1 2.2 2.7 2.8 3.6 4 5.6

iC60L-MA

0.7

0.2

0.6

0.9 1.1 1.5

1.6

0.8

2

2.3

1.9

2.2 2.4 2.7

1.8

2.5 3 3.1 3.5 3.6 4 5.6

RCCB

iID 2P

0.8

0.9

2.6

2.6 3 5

4P

0.7

1.9

1.5 2.6 4.3

2.7

3.6

5.6

Add-on residual current devices

Vigi iC60 10 mA

3

30 mA

1.4

1.1

2.3

100 mA

1.1

2.3

300 mA

1.3

0.9

2.3

500 mA

1.1

0.9

2.3

1000 mA

2.3

Contactors

iCT/iCT+ Power circuit

0.6 0.9 1.4

1.5

3.4

4

Impulse relays

iTL/iTL+ Power circuit

0.6

1.5

Push-buttons

iPB

0.6

Selector switches

iSSW

0.8

iCMA/iCMB/iCMC/

iCMD/iCMV

0.4

Switch-disconnectors

iSW

0.8

1.3 1.1

1.8

3.4 4.2

iSW-NA 2P

0.7

1.8

3 5

4P

0.6

1.5

2.5 4.1

Indicator lights

iIL

0.3

Note: When the enclosure's thermal balance, consider the 4P devices load is only on 3 phases

Impedance calculation:

Z = P / I²

Z: impedance in Ohms

P: dissipated power in Watts (table values)

I: rating in Amperes

Voltage drop calculation:

U = P / I

U: voltage drop in Volts

P: dissipated power in Watts (table values)

I: rating in Amperes

The following table indicates the average dissipated power per pole in W for a

current equal to the rating of the device and at the operating voltage.