Dimensions
Section 12
Dissipated power, impedance and
voltage drop
Technical advice
Rating (A)
0.5 1 1.6 2 2.5 3 4 6 6.3 10 12.5 13 16 20 25 32 40 50 63 80 100 125
Circuit breakers
iC60
2.3 2.3
1.9
2.2 2.4 1.3
2
2 2.1 2.2 2.7 2.8 3.6 4 5.6
iC60L-MA
0.7
0.2
0.6
0.9 1.1 1.5
1.6
0.8
2
2.3
1.9
2.2 2.4 2.7
1.8
2.5 3 3.1 3.5 3.6 4 5.6
RCCB
iID 2P
0.8
0.9
2.6
2.6 3 5
4P
0.7
1.9
1.5 2.6 4.3
2.7
3.6
5.6
Add-on residual current devices
Vigi iC60 10 mA
3
30 mA
1.4
1.1
2.3
100 mA
1.1
2.3
300 mA
1.3
0.9
2.3
500 mA
1.1
0.9
2.3
1000 mA
2.3
Contactors
iCT/iCT+ Power circuit
0.6 0.9 1.4
1.5
3.4
4
Impulse relays
iTL/iTL+ Power circuit
0.6
1.5
Push-buttons
iPB
0.6
Selector switches
iSSW
0.8
iCMA/iCMB/iCMC/
iCMD/iCMV
0.4
Switch-disconnectors
iSW
0.8
1.3 1.1
1.8
3.4 4.2
iSW-NA 2P
0.7
1.8
3 5
4P
0.6
1.5
2.5 4.1
Indicator lights
iIL
0.3
Note: When the enclosure's thermal balance, consider the 4P devices load is only on 3 phases
Impedance calculation:
Z = P / I²
Z: impedance in Ohms
P: dissipated power in Watts (table values)
I: rating in Amperes
Voltage drop calculation:
U = P / I
U: voltage drop in Volts
P: dissipated power in Watts (table values)
I: rating in Amperes
The following table indicates the average dissipated power per pole in W for a
current equal to the rating of the device and at the operating voltage.
Acti 9products