2/10
Technical
Section 11
Dimensions
Section 12
2
Vigi iC60 add-on residual
current devices (type A) (cont.)
Protection
Earth leakage protection
IEC/EN 61009-1
b
b
Combined with iC60 circuit breaker, the Vigi iC60 provide:
v
v
protection of persons against electric shock by direct contact (30 mA),
v
v
protection of persons against electric shock by indirect contact (
u
100 mA),
v
v
protection of installations against the risk of fire (300 mA or 500 mA)),
v
v
use with 2 pole or 4 pole iC60H only.
PB104471-35
Catalogue numbers
Vigi iC60 add-on residual current devices
Type
A
Width in 9 mm
modules
Product
Vigi iC60
Auxiliaries
Without auxiliaries
2P
Sensitivity 30 mA
100 mA 300 mA 500 mA 300 mA
s
1000 mA
s
DB122462
Rating 25 A
A9V51225 A9V22225 A9V54225 A9V26225 -
-
3
63 A
A9V51263 A9V22263 A9V54263 A9V26263 A9V25263 A9V29263
4
4P
Sensitivity 30 mA
100 mA 300 mA 500 mA 300 mA
s
1000 mA
s
DB122464
Rating 25 A
A9V51425 A9V22425 A9V54425 A9V26425 -
-
6
63 A
A9V51463 A9V22463 A9V54463 A9V26463 A9V25463 A9V29463
7
Voltage rating (Ue)
230 - 240 V, 400 - 415 V
Operating frequency
50/60 Hz
PB104466-35