Background Image
Table of Contents Table of Contents
Previous Page  26 / 408 Next Page
Information
Show Menu
Previous Page 26 / 408 Next Page
Page Background

2/6

Technical

Section 11

Dimensions

Section 12

iC60H2 RCBO

10,000A

30mA

Protection

Circuit protection

2

b

b

The 2-pole iC60H2 RCBO’s self-contained residual current device carries out

b

b

complete protection of final circuits:

v

v

protection against short-circuits and cable overloads,

v

v

protection of persons against electric shock by direct contact

(30 mA sensitivities),

v

v

protection of equipment against fires set by leakage currents

(300 mA sensitivity).

b

b

iC60H2 RCBO switches neutral, together with phase. It is therefore suitable for all

circuits, whatever the earthing system (except for TN-C).

IEC 61009-1,

IEC 61009-2-2,

AS/NZS 61009.1

Catalogue numbers

iC60H2 RCBO 10000

2P

A

Width in 9-mm

modules

C curve

Voltage rating (V)

Sensitivity (I

Δ

n) 30 mA

DB405040

N/L

1in

L

2in

N/L

1out

L

2out

110

Rating

(In)

10 A

A9D19210

4

16 A

A9D19216

20 A

A9D19220

25 A

A9D19225

32 A

A9D19232

240

Rating

(In)

10 A

A9D11210

16 A

A9D11216

20 A

A9D11220

25 A

A9D11225

32 A

A9D11232

Operating frequency

50…60 Hz

Alternating current (AC) 50/60 Hz

Breaking capacity (Icn) according to IEC 61009-1

Voltage (Ue)

Ph/N, Ph/Ph

110 V

240 V

Rating (In)

10 to 32 A

10000 A

10000 A

PB111076-70

Accessory

Padlocking device

b

b

A9A27049 for pack of 10. Used to lock the toggle in the "open" or "closed"

position by 4 mm diameter padlock (not supplied).