Background Image
Table of Contents Table of Contents
Previous Page  24 / 408 Next Page
Information
Show Menu
Previous Page 24 / 408 Next Page
Page Background

2/4

Technical

Section 11

Dimensions

Section 12

iC60H circuit breakers

(curve B, C, D) (cont.)

Protection

Circuit protection

2

Connection

Without accessory With accessories

DB405585

Rating Tightening

torque

Copper cables

50 mm²

Al

terminal

Screw-on

connection

for ring

terminal

Multi-cables terminal

Rigid

Flexible

or ferrule

Rigid

cables

Flexible

cables

1 to 25 A

2 N.m

1 to 25 mm

2

1 to 16 mm

2

-

Ø 5 mm

-

-

32 to 63 A

3.5 N.m 1 to 35 mm

2

1 to 25 mm

2

50 mm

2

3 x 16 mm

2

3 x 10 mm

2

DB122945

DB122946

6.5 mm

14 mm

DB122935

DB118789

DB118787

PZ2

Technical data

Main characteristics

According to IEC/EN 60947-2

Insulation voltage (Ui)

500 V AC

Pollution degree

3

Rated impulse withstand voltage (Uimp)

6 kV

Thermal tripping Reference temperature 50°C

Magnetic tripping B curve

4 In ± 20 %

C curve

8 In ± 20 %

D curve

12 In ± 20 %

Utilization category

A

According to IEC/EN 60898-1

Limitation class

3

Rated making and breaking capacity of an

individual pole (Icn1)

Icn1 = Icn

Additional characteristics

Breaking capacity

under 1 pole with IT

380-415 V isolated

neutral system

(case of double fault)

40 A

4 kA

50/63 A

3 kA

Degree of protection

(IEC 60529)

Device only

IP20

Device in modular

enclosure

IP40

Insulation classe II

Endurance (O-C)

Electrical

10,000 cycles

Mechanical

20,000 cycles

Overvoltage category (IEC 60364)

IV

Operating temperature

-35°C to +70°C

Storage temperature

-40°C to +85°C

Tropicalization (IEC 60068-1)

Treatment 2 (relative humidity 95 % to 55°C)

DB123310

DB123312

Clip on DIN rail 35 mm.

Indifferent position of installation.

DB123314

IP20

IP40

Weight (g)

Circuit-breaker

Type

iC60H

1P

125

2P

250

3P

375

4P

500

Dimensions (mm)

DB405584

72

54

36

50

5.5

85

4.6

64

69.5

78.5

18

4P

3P

2P

1P

45