2/16
Technical
Section 11
Dimensions
Section 12
2
Technical data
Main characteristics
Insulation voltage (Ui)
500 V
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6 kV
According to IEC/EN 61008-1
Making and breaking capacity (Im/I
D
m)
1500 A
Surge current
withstand (8/20 μs)
without tripping
AC and A types (no selective
s
)
250 Â
AC, A types (selective
s
)
3 kÂ
SI
type
3 kÂ
Conditional rated
short circuit current
(Inc/I
D
c)
With C60H
15 kA
With fuse
10,000 A
Additional characteristics
Degree of protection Device only
IP20
Device in modular enclosure
IP40
Insulation classe II
Endurance (O-C)
Electrical (AC1) 16 to 63 A 15,000 cycles
80 to 100 A 10,000 cycles
Mechanical
20,000 cycles
Operating
temperature
AC type
-5°C to +60°C
A and
SI
types
-25°C to +60°C
Storage temperature
-40°C to +85°C
Connection
Without accessory With accessories*
DB122947
Type Tightening
torque
Copper cables
50 mm²
Al
terminal
Screw-on
connection
for ring
terminal
Multi-cables terminal
Rigid
Flexible
or ferrule
Rigid
cables
Flexible
cables
iID
3.5 N.m 1 to 35 mm
2
1 to 25 mm
2
50 mm
2
Ø 5 mm 3 x 16 mm
2
3 x 10 mm
2
DB122945
DB122946
PZ2
14 mm
DB122935
DB118789
DB118787
6.5 mm
DB123310
DB123312
Clip on DIN rail 35 mm.
Indifferent position of installation.
DB123314
IP20
IP40
iID residual current
circuit breakers (AC, A,
SI
types) (cont.)
Protection