2/22
Technical
Section 11
Dimensions
Section 12
2
Indication
Auxiliaries
iOF
iSD
iOF/SD+OF
iOF+SD24
Type
Open/close
auxiliary contact
Fault indicating contact
Double open/close or fault
indicating contact
Double open/close and
fault indicating contact
Function
b
b
Changeover contact
indicates "open" or "closed"
position of the breaker
b
b
Changeover contact
indicates position of the
breaker; upon:
v
v
electrical fault
v
v
action on tripping auxiliary
b
b
Same indication as
VISI-TRIP
b
b
The iOF/SD+OF auxiliary is a
2-in-1 product: via a mechanical
selector switch, it provides two
contacts, OF+SD or OF+OF
b
b
2 contacts (1 NO + 1 NC)
can report the signalling
information of the associated
device to the Acti 9 Smartlink
or a programmable logic
controller:
v
v
electrical fault
v
v
actuation of the tripping
auxiliary
v
v
"Open" or "Closed"
position of the associated
device
Wiring diagrams
OF position
SD position
Use
b
b
Remote indication of
the position of the associated
breaker
b
b
Remote indication of
tripping upon a fault of the
associated breaker
b
b
Remote indication of position
and/or tripping upon a fault of the
associated breaker
b
b
Remote indication of
position and tripping upon a
fault of the associated
breaker
Catalogue numbers
A9A26924
A9A26927
A9A26929
A9A26897
iC60, iID, iDPN Vigi, RCA and
ARA
b
b
b
b
b
b
b
b
Technical specifications
Rated voltage (Ue) V AC
240…415
240…415
240…415
-
V DC
24…130
24…130
24…130
24
Operating
frequency
Hz
50/60
50/60
50/60
-
Red mechanical indicator
–
On front face
On front face
On front face
Test function
On toggle
On toggle
On toggle
On toggle
Width in 9 mm modules
1
1
1
1
Operating current
24 V DC 10 mA mini, 6 A maxi
2 mA mini, 50 mA maxi
48 V DC 2 A
-
60 V DC 1.5 A
-
130 V DC 1 A
-
240 V AC 6 A
-
415 V AC 3 A
-
Number of contacts
1 NO/NC
1 NO/NC
1 NO/NC + 1 NO/NC
1 NO/NC
Operating
temperature
°C
-35…+70
-35…+70
-35…+70
-25…+70
Storage
temperature
°C
-40…+85
-40…+85
-40…+85
-40…+85
DB118811
DB118812
DB118810
DB118813
DB124318
PB104474-35
PB104476-35
PB104475-35
PB107750-35
Electrical auxiliaries for
iC60, iID, iDPN Vigi, RCA and ARA
(cont.)
Protection
Circuit protection
Earth leakage protection