Background Image
Table of Contents Table of Contents
Previous Page  262 / 408 Next Page
Information
Show Menu
Previous Page 262 / 408 Next Page
Page Background

8/20

Technical

Section 11

Dimensions

Section 12

8

Powerpact 4 panelboards

Metering facilities for

incoming and outgoing

circuits

The arrangement consists of side extension boxes that house the meters and also

provide additional cabling space. Meters and current transformers are ordered

separately to meet the needs of the installation. The necessary cable looms are

included wi th the steelwork. The meters are mounted on hinged doors. The box also

contains the auxiliary busbar that provides the 240V control supply for the meters. The

left hand extensions have sufficient meter positions for half the number of outgoing

ways. The right hand extensions have positions for half the number of outgoing ways

plus three additional positions. These extra positions may be used for additional

metering or mounting surge arresters, control fuses etc. The lower two positions have a

transparent window and DIN rail. This can be removed if not required.

Note: the meters, CT modules and surge arresters must be ordered separately

Incoming and outgoing metering for boards up to 630A

(This arrangement is not applicable for boards fitted with MGPINC direct connections).

When both incoming and outgoing metering is required there is a very cost effective

solution by incorporating the incoming metering into the right hand side extension box.

Components required are:

n

Standard extension box MG6CEX to provide the required cable spreading space

n

Current transformer module to fit on line side of incoming breaker.

n

PM750MG meter.

n

Two MGPC2025 corner units, optional

The meter should be cabled to the CT module according to the diagram supplied.

(loom not supplied). The auxiliary supply to the meter should be taken from one phase

and neutral and must be suitably fused.

Note. A warning notice should be placed in the board as the voltage connections are

taken off the live side of the main breaker.

MG6Cxx 630A board

Incoming metering kit 400A

MG64M

630A

MG66M

MG8Cxx 800A board

Incoming metering kit 800A

MG88M

MG88MX - less meter

630A & 800A outgoing metering side extension boxes

6 way board

Left hand side (*)

3 meter positions

MGPCM6L

Right hand side (*) 7 meter positions

MGPCM6R

12 way board

Left hand side (*)

6 meter positions

MGPCM12L

Right hand side (*) 9 meter positions

MGPCM12R

18 way board

Left hand side (*)

9 meter positions

MGPCM18L

Right hand side (*) 11 meter positions

MGPCM18R

(*) When the board is inverted for top entry main cables these side extensions fit

on the other side of the board.

Accessories

Cable loom

MGPCML

Meter blanks

03908

MG2C* 250A board

Incoming metering kit 250A

MG6CEXM

Ordering references

250A powerboard with metering facility

13 SP positions

MG25C2M

17 SP positions

MG25C4M

250A Panelboard

Incoming/Outgoing metering

The metering extension box allows for metering for the incoming and outgoing

devices to be metered. The kit comes complete with a fuse holder and wiring looms

to provide power to the meters. The meters and CT modules are ordered separately.

630 & 800A Panelboards

Incoming metering

This is easily added to a board when it is first being installed. The kit comprises

an extension box that houses the meter and, when fitted to the same end of the

board as the incomer, provides additional space for the main incoming cables. All

components including the meter, CTs and wiring is included in the kit. The meter is

fully set up for the CT ratio and the voltage configuration.

Outgoing circuit metering

Metering can be fitted to some or all of the three phase outgoing circuits on 630A &

800A boards whether the boards are fitted with incoming metering or not.