8/18

Technical

Section 11

Dimensions

Section 12

8

Powerpact 4 panelboards

Accessories

Connection accessories

Bare cable connectors

Capacity

Breaker

Part number

Set of 3 Set of 4

1.5 - 95mm

2

160

LV429242 LV429243

10 - 185mm

2

250

LV429259 LV429260

35 - 300mm

2

630

LV432479 LV432480

2 x 95 - 240mm

2

630

LV432481 LV432482

Crimp cable lugs supplied with phase barriers

120mm

2

copper

250

LV429252 LV429256

150mm

2

copper

250

LV429253 LV429257

185mm

2

copper

250

LV429254 LV429258

240mm

2

copper

630

LV432500 LV432501

300mm

2

copper

630

LV432502 LV432503

150mm

2

aluminium

250

LV429504 LV429505

185mm

2

aluminium

250

LV429506 LV429507

240mm

2

aluminium

630

LV432504 LV432505

300mm

2

aluminium

630

LV432506 LV432507

Spreaders

A

Pole pitch mm Quantity

Part number

250

45

Set of 3

LV431563

250

45

Set of 4

LV431564

630

52.5

Set of 3

LV432490

630

52.5

Set of 4

LV432491

Auxiliary switch

for 3 or 4 pole devices only

n

For all MCCBs

n

Used to indicate open, closed or tripped status

n

SDE adaptor required for trip unit devices up to 250A TM or MA (to indicate

trip on overcurrent).

Two

auxiliary switches will be needed to indicate open,

closed

and

tripped status

Part number

Auxiliary changeover switch

29450

SDE adaptor

29451

Voltage releases to fit all MCCBs 16/630A

for 3 or pole

devices only

AC 50/60Hz

Voltage

(V)

Part number

Shunt trip

(MX)

Undervoltage release

(MN)

200/240

LV429387

LV429407

380/415

LV429388

LV429408

Other voltages available - refer to Compact NSX catalogue.

Terminal shields

Current rating (A)

Part number

Up to 160A single pole and 250A neutral link

LV429320

Up to 160A 2 pole

LV429320

x 2

Up to 250A 3 pole (single) long

LV429517

Up to 250A 4 pole (single) long

LV429518

Up to 400/630A 3 pole (single)

LV432593

Up to 400/630A 4 pole (single)

LV432594

For shielding a TP MCCB with neutral lnik use the 4 pole terminal shield.

Single pole shrouding plates

MGPBBP

MGPBB25

Single pole shrouding plates are

required for each unoccupied

outgoing way.

In addition a 25mm shrouding plate is always

required when 4 pole 400A or 630A circuit

breakers are mounted on the outgoing pan

assembly.

Boards up to 800A are supplied with 3 x MGPBBP. 1600A board is supplied

with 6 x MGPBBP.