8/24

Technical

Section 11

Dimensions

Section 12

8

Power Meter functions

Electronic Micrologic 5E

Functions and

characteristics

Micrologic 5 / 6 integrated Power Meter functions

Display

E

Micrologic

LCD

FDM121

display

Display of protection settings

Pick-ups (A) and

delays

All settings can be displayed

Ir, tr, Isd, tsd, Ii, Ig, tg

b

b

Measurements

Instantaneous rms measurements

Currents (A)

Phases and neutral

I1, I2, I3, IN

b

b

b

Average of phases

Iavg = (I1 + I2 + I3) / 3

b

-

b

Highest current of the 3 phases and

neutral

Imax of I1, I2, I3, IN

b

b

b

Ground fault (Micrologic 6)

% Ig (pick-up setting)

b

b

b

Current unbalance between phases % Iavg

b

-

b

Voltages (V)

Phase-to-phase

U12, U23, U31

b

b

b

Phase-to-neutral

V1N, V2N, V3N

b

b

b

Average of phase-to-phase voltages Uavg = (U12 + U21 + U23) / 3

b

-

b

Average of phase-to-neutral

voltages

Vavg = (V1N + V2N + V3N) / 3

b

-

b

Ph-Ph and Ph-N voltage unbalance % Uavg and % Vavg

b

-

b

Phase sequence

1-2-3, 1-3-2

b

b

b

Frequency (Hz)

Power system

f

b

b

b

Power

Active (kW)

P, total / per phase

b

b

b

Reactive (kVAR)

Q, total / per phase

b

b

b

Apparent (kVA)

S, total / per phase

b

b

b

Power factor and cos

j

(fundamental) PF and cos

j

, total and per phase

b

-

b

Maximeters / minimeters

Associated with instantaneous rms

measurements

Reset via Micrologic or FDM121

display unit

b

-

b

Energy metering

Energy

Active (kW), reactive (kVARh),

apparent (kVAh)

Total since last reset

b

b

b

Absolute or signed mode

(1)

Demand and maximum demand values

Demand current (A)

Phases and neutral

Present value on the selected window

b

-

b

Maximum demand since last reset

b

-

b

Demand power

Active (kWh), reactive (kVAR),

apparent (kVA)

Present value on the selected window

b

-

b

Maximum demand since last reset

b

-

b

Calculation window

Sliding, fixed or com-synchronised Adjustable from 5 to 60 minutes in 1

minute steps

b

-

(2)

Power quality

Total harmonic

distortion (%)

Of voltage with respect to rms value THDU,THDV of the Ph-Ph and Ph-N

voltage

b

-

b

Of current with respect to rms value THDI of the phase current

b

-

b

(1) Absolute mode: E absolute = E out + E in; Signed mode: E signed = E out - E in.

(2) Available via the communication system only.

Additional technical characteristics

Measurement accuracy

Accuracies are those of the entire measurement system, including the sensors:

b

b

Current: Class 1 as per IEC 61557-12

b

b

Voltage: 0.5 %

b

b

Power and energy: Class 2 as per IEC 61557-12

b

b

Frequency: 0.1 %