Powerpact 4 panelboards

Introduction

Technical

Section 11

Dimensions

Section 12

NSX moulded case circuit breakers

Powerpact 4 panelboards have a unique interconnection system which

automatically gives the correct torque settings. 1, 2, 3, and 4 pole devices may be

mixed to suit the installation needs without loss of space.

Metering

n

A PowerLogic PM5000 series multi-function digital meter is fitted as standard

to monitor the incoming supply on style G and as an option on other styles.

It is also used for all outgoing metering. Readings available voltage, current,

frequency, power, energy, demand values and harmonic distortion. The meter

also provides a pulse output for kWh and kVArh.

n

A side extension cubicle may be fitted on styles D/E/G which has provision

for metering outgoing circuits, refer to metering on page 2/18. This cubicle also

acts as a cable extension box.

Technical data for circuit breakers

Manufactured and tested to BS EN 60947-2

Ics

100% Icu 16 - 630A, 75% Icu 800 - 1600A

Calibration temperature

40

0

C

Thermal adjustment

16 - 250A = 0.7 - 1 x In

(3 and 4 pole)

400 - 630A = 0.4 - 1 x In

800 – 1600A = 0.4 x In

MCCB Icu & terminal size

16 - 100A 36kA 6mm bolt

160 - 250A 36kA 8mm bolt

400 - 630A 50kA 10mm bolt

800 – 1600 50kA 2 x 12mm bolts

Earth fault protection

n

May be added to any 4 pole MCCB

n

Sensitivities 30, 300mA 1, 3, 10A

n

Time delay 0, 60, 150, 310 milli - seconds

800/1250/1600A breakers

800/1250/1600A breakers are fitted with Micrologic 5.0 control units to enable full

discrimination with the outgoing breakers to be obtained. Alternative control units

may be fitted if required.

250A panelboards

The main incoming device is side mounted at the bottom right hand side. If a 4

pole incomer is used the number of outgoing ways available is reduced by one

single pole way. The incoming terminal shroud can be positioned to suit a 3 or 4

pole incoming breaker.

250A powerboard

One 3 pole terminal shield for a 250A breaker is supplied as standard for the main

incoming terminals. Two adjacent 3 or 4 pole toggle operated breakers may be

mechanically interlocked using Part number LV429354.

400/630A panelboard

The line (supply) terminals on the incoming device must be suitably shrouded.

The board is supplied with 1 or 3 pole shroud for a 400/630A breaker. For other

breakers suitable terminal shields should be ordered separately:

250A 3 pole LV429323

250A 4 pole LV429324

400/630A 4 pole LV432595

These terminal shields are supplied singly.