Page Background

8

8/5

Powerpact 4 panelboards

Circuit breaker

installation

Technical

Section 11

Dimensions

Section 12

The 4 pole busbar system ready to accept the circuit

breaker.

The circuit breaker is placed in the panelboard and

pushed up to the busbars. 1P, 2P, 3P and 4 pole

breakers may be mixed in any order on the busbars.

The circuit breaker fixing screw is fitted and tightened

to retain the breaker in the board.

Retaining screw M5 8.5mm long.

The connections to the busbars are tightened until the

tops of the connection bolts shear off. This ensures

that the correct torque has been applied to the

connections.

The circuit breaker is now mechanically & electrically

connected in the panel board. It is now ready for the

outgoing cables.

Note how the breaker cassette fully shrouds the

busbars. Unused positions must be fitted with blanking

plates.

To remove (17mm bi-hexagonal socket)

RS number 572-864 (1/2”)