Background Image
Table of Contents Table of Contents
Previous Page  233 / 408 Next Page
Information
Show Menu
Previous Page 233 / 408 Next Page
Page Background

7/101

Technical

Section 11

Dimensions

Section 12

7

CT,

Ip/5A ratio (cont.)

Current

transformers

CT selection - Electrical aspect Ip/5 A

b

b

We recommend that you choose the ratio immediately higher than the maximum

measured current (In).

Example:

In = 1103 A; ratio chosen = 1250/5.

b

b

For small ratings:

from 40/5 to 75/5 and for an application with digital devices, we recommend

that you choose a higher rating, for example 100/5.

This is because small ratings are less accurate and the 40 Ameasurement,

for example, will be more accurate with a 100/5 CT than with a 40/5 CT.

b

b

Specific case of the motor starter:

to measure motor starter current, you must choose a CT with primary current

Ip = Id/2 (Id = motor starting current).

Validation of measurement solution according

accuracy class

It consists in controlling the right adaptation of the CT on the assucary class aspect.

The accuracy class is specified in the project. The total dissipated power of the

measurement circuit (meter + cables) should not be superior to the specified limit of

the CT. This limit is for different standard classes. If necessary, the choice of the

cable section, the CT or meter should be modify to fit the requirement.

Copper cable

cross-section

(mm

2

)

Power per doubled

meter at 20 °C

(VA)

Schneider Electric

device

Consumption of

the current input

(VA)

Ammeter

72 x 72 / 96 x 96

1.1

Analogue ammeter

1.1

Digital ammeter

0.3

PM700, PM800

0.15

PM3000

0.3

1

1

1.5

0.685

2.5

0.41

4

0.254

6

0.169

10

0.0975

16

0.062

For each temperature variation per 10 °C

bracket, the power drawn up by the cables

increases by 4 %.

Application example

Project specification:

200 A

, in

Ø27

mm cable, accuracy class 1.

Our choice is

METSECT5MA020

.

For this CT selected on the chart (next page), the max acceptable power is

7 VA

(for

"Accuracy class 1" which is specified in the project).

Internal

profile

type

Cables

(mm)

Bars

(mm)

Rating

Ip/5 A

(A)

Cat. no.

Accuracy class

0.5 1

3

Max. power (VA)

MA

Ø27

10 x 32

15 x 25

150

METSECT5MA015

3

4

-

200

METSECT5MA020

4

7

-

250

METSECT5MA025

6

8

-

300

METSECT5MA030

8

10 -

400

METSECT5MA040

10 12 -

Control of the conformity of the measurement chain:

b

b

PM3000 multi-meter: 0.3 VA.

b

b

4 meters of 2.5 mm

2

, doubled wires: 0.41 x 4 = 1.64 VA.

Total:

0.3 + 1.64 = 1.94 VA (< 7 VA)

Conclusion:

this CT is well adapted as the accuracy class will be even better than 1.