Technical

Section 11

Dimensions

Section 12

7

CT,

Ip/5A ratio

Current

transformers

The Ip/5A ratio current transformer delivers at the secondary a current (Is) of 0 to 5 A

that is proportional to the current measured at the primary (Ip).

This allows them to be used in combination with measurement equipment:

b

b

ammeters

b

b

kilowatt-hour meters

b

b

measurement units

b

b

control relays

b

b

etc.

When the primary is energized, the measurement equipment nearly acts as a short

circuit which keeps the secondary voltage very low. This voltage will increases

significantly if the short circuit is removed.

CT selection - conductor rating aspects

The choice depends on the conductor profile and the maximum intensity

of the primary circuit.

CT with let-through primary

Conductor type Cable

Mixed, bars or cables

Vertical or horizontal bars

Vertical bars

Suggested

Current

Transformer

and mounting

DB415986.eps

DB415920.eps

DB415988.eps

DB415989.eps

DB415921.eps

DB415987.eps

Ratings (A)

40 to 250

150 to 800

200 to 4000

500 to 600

5000 to 6000

CT internal

profile

Type C

Type M

Type D

(1)

Type V

MA

MB

MC

VF

VV

MD

ME

MF

(1)

Two secondary connectors (parallel internal wiring - only one secondary winding) for easier

cable access. 1 lateral + 1 on one extremity. Warning: only one must be used at a time.

Specific mounting: use of cylinder

A cylindrical metallic spacer ensures a proper CT positioning when the conductor or

the CT cannot be positioned perpendicular. Secured by bolt + nut.

CT with primary connection by screw and nut

(example: use of cylinder with bar or cable)

DB416006.eps

DB416005.eps

16550 (brass)

METSECT5CYL1 (aluminium)

Ip

Is

Primary

circuit

Secondary

circuit

N

Ph

Measurement

equipment

Load

DB416186.eps

Application diagram of a CT.