Background Image
Table of Contents Table of Contents
Previous Page  228 / 408 Next Page
Information
Show Menu
Previous Page 228 / 408 Next Page
Page Background

7/96

Technical

Section 11

Dimensions

Section 12

7

Power Meter Series PM3200

Functions and characteristics (cont.)

Basic metering

Specifications

(continued)

PM3200 Range

Mechanical characteristics

Weight

0.26kg

IP degree of protection (IEC60529)

IP40 front panel, IP20 meter body

Dimension

90 x 95 x 70mm

Environmental conditions

Operating temperature

-25 ºC to +55 ºC

Storage temperature

-40 ºC to +85 ºC

Humidity rating

5 to 95% RH at 50ºC (non-condensing)

Pullution degree

2

Metering category

III, for distribution systems up to 277/480VAC

Dielectric withstand

As per IEC61010-1, Doubled insulated front panel display

Altitude

3000m max

Electromagnetic compatibility

Electrostatic discharge

Level IV (IEC61000-4-2)

Immunity to radiated fields

Level III (IEC61000-4-3)

Immunity to fast transients

Level IV (IEC61000-4-4)

Immunity to surge

Level IV (IEC61000-4-5)

Conducted immunity

Level III (IEC61000-4-6)

Immunity to power frequency magnetic fields 0.5mT (IEC61000-4-8)

Conducted and radiated emissions

Class B (EN55022)

Safety

CE as per IEC61010-1

(1)

Communication

RS485 port

Half duplex, from 9600 up to 38400 bauds, Modbus RTU (double insulation)

Display characteristics

Dimensions (VA)

43mm x 34.6mm

Display resolution

128 x 96 dots

Standard compliance

IEC61557-12, EN61557-12

IEC61010-1, UL61010-1

IEC62052-11, IEC62053-21, IEC62053-22, IEC62053-23

EN50470-1, EN50470-3

(1) Protected throughout by double insulation

Multi-tariff capability

The PM3200 range allows arrangement of kWh

consumption in four different registers. This can be

controlled by:

b

Digital Inputs. Signal can be provided by PLC or utilities

b

Internal clock programmable by HMI

b

Through communication

This function allows users to:

b

Make tenant metering for dual source applications to

differentiate backup source or utility source

b

Understand well the consumption during working time

and non working time, and between working days and

weekends

b

Follow up feeders consumption in line with utility tariff

rates

Power Meter Series PM3250