Background Image
Table of Contents Table of Contents
Previous Page  144 / 408 Next Page
Information
Show Menu
Previous Page 144 / 408 Next Page
Page Background

iCT contactors

Electrical auxiliaries for iCT (cont.)

Control

Remote control

7/12

Technical

Section 11

Dimensions

Section 12

Control and indication

Auxiliary

iACT24

Type

Control and indication 24 V DC

With Ti24 connector

Function

b

b

This auxiliary allows a contactor to be interfaced with the Acti 9 Smartlink interface or a programmable logic controller (PLC)

in 24 V DC (control, O/C indication)

b

b

230 V AC control

Wiring diagrams

In In

Out

24V

Ti24

Y3 24V O/C 0V

OFF

Auto

ON

iACT24

P

P

In In

Out

24V

Ti24

Y3 24V O/C 0V

iACT24

P

P

Wiring with exclusive selector

230 V AC control (Y1 = 0) / 24 V DC control (Y1 = 1)

Wiring for non-exclusive 230 V AC and 24 V DC controls

Mounting

b

b

To the left of the iCT contactor using the yellow clips

(1)

.

b

b

When an iACT24 is used, the A1/A2 terminals of the contactors should not be wired. Only the yellow clips integral with the iACT24

should be used for connection to the coil.

Utilization

b

b

230 V AC interface:

v

v

Y1: enabling of 24 V DC control (Y1 = 1) or inhibition of 24 V DC control (Y1 = 0).

v

v

Y2: 230 V pulse control

b

b

"Ti24" 24 V DC interface:

v

v

Y3: 24 V DC control of iCT closing on rising edge and opening on falling edge

v

v

reading of the contactor status (opened or closed) from the position of the integrated O/C auxiliary contact

v

v

monitoring of connection of the "Ti24" terminal block by the upstream system (PLC, supervision system) via the 24 V terminal (in the

centre of the Ti24 terminal block)

Catalogue numbers

A9C15924

Technical specifications

Control voltage (Ue) V AC 230, +10 %, -15 % (Y2)

V DC 24, ± 20 % (Y3)

Control voltage

frequency

Hz

50/60

Insulation voltage

(Ui)

V AC 250

Rated impulse

withstand voltage

(Uimp)

kV

8 (OVC IV)

Pollution degree

3

Degree of protection

IP20B device only

IP40 device in modular enclosure

Width in 9 mm modules

2

Auxiliary contact (O/C) Ti24 24 V DC protected output, min. 2 mA, max. 100 mA

Contact

1 O/C operating category AC 14

Operating

temperature

°C -25°C to +60°C

Storage

temperature

°C -40°C to +80°C

Consumption

<1 W

Standard

IEC/EN 60947-5-1

(1) Mechanical and electrical link.

PB107751-34

DB124313

DB124441

Acti 9 Smartlink or PLC

Acti 9 Smartlink or PLC

24 V DC

24 V DC

0 V

0 V

7