7/8
Technical
Section 11
Dimensions
Section 12
7
DB123309
DB123300
Clip on DIN rail 35 mm.
± 30° vertical.
Technical data
Power circuit
Voltage rating (Ue)
1P, 2P
250 V AC
3P, 4P
400 V AC
Frequency
50 Hz
Type of load
See technical section
Endurance (O-C)
Electrical
100,000 cycles
Maximum number of switching operation a day 100
Additional characteristics
Insulation voltage (Ui)
500 V AC
Pollution degree
2
Rated impulse withstand voltage (Uimp)
2.5 kV (4 kV for 12/24/48 V AC)
Degree of protection
(IEC 60529)
Device only
IP20
Device in modular
enclosure
IP40
Operating temperature
-5°C to +60°C
(1)
Storage temperature
-40°C to +70°C
Tropicalization (IEC 60068-1)
Treatment 2 (relative humidity 95 % at 55°C)
ELSV compliance (Extra Low Safety Voltage) for 12/24/48 V AC versions
The product control conforms to the SELV (safety extra low voltage) requirements
(1) In the case of contactor mounting in a enclosure for which the interior temperature is in range
between 50°C and 60°C, it is necessary to use a spacer, cat. no. A9A27062, between each
contactor
DB123311
IP20
IP40
DB123331
Spacer cat. no. A9A27062
iCT contactors (cont.)
Control
Remote control