Background Image
Table of Contents Table of Contents
Previous Page  142 / 408 Next Page
Information
Show Menu
Previous Page 142 / 408 Next Page
Page Background

7/10

Technical

Section 11

Dimensions

Section 12

7

iCT contactors

Electrical auxiliaries for iCT

Control

Remote control

Indication

Protection

Control

Auxiliaries

iACTs

iACTp

iACTc

Type

Indication

Interference filtering

Impulse/latched control

With Open/Close auxiliary contact

2 protection circuits

Function

b

b

This auxiliary allows indication of the "open"

or "closed" position of the contactor power contacts

b

b

This auxiliary is an interference

suppressor which limits overvoltages

on the control circuit

b

b

This auxiliary, combined with contactors,

enables them to be controlled by

2 order types:

v

v

impulse order for local control (input T)

v

v

latched order for centralised control

(input X)

v

v

the last order received takes priority

Wiring diagrams

23 11

24 12

12 14

13

13 23

14 24

3 1

4 2

T

X

Mounting

b

b

Mounted to the right of iCT

b

b

Mounted to the left of iCT

by yellow clips

(1)

b

b

By wires

b

b

Mounted to the left of iCT

by yellow clips

(1)

Use

b

b

The iACTp has 2 separate and

identical circuits, allowing it to be

combined with 2 different one on the

iCT the other by wires

b

b

Mains power outages:

v

v

< 70 ms: keeps its initial status

v

v

> 80 ms: reset

v

v

put back into operation by manual

operation on input X or T.

b

b

Minimum impulse duration: 250 ms

Catalogue numbers

A9C15914

A9C15915

A9C15916

A9C15918 A9C15919 A9C15920 A9C18308 A9C18309

Technical specifications

Control voltage

(Ue)

V AC 24…240

48 …127 12 …48 220 …240 230…240 24…48

V DC 24…130

Control voltage

frequency

Hz 50/60

50/60

50/60

Width in 9 mm modules 1

2

2

Auxiliary contact

(breaking capacity)

b

b

Mininimum: 10 mA at 24 V DC/AC - cos

ϕ

= 1

b

b

Maximum:

v

v

5 A at 240 V AC - cos

ϕ

= 1

v

v

1 A at 130 V DC

Number of contacts

1NO + 1NC 1CO

2NO

Operating

temperature

°C -5°C to +50°C

Storage

temperature

°C -40°C to +70°C

Consumption

OFF load: 3 VA

Inrush

(2)

: 2 VA

Holding

(2)

: 0.2 VA

(1) Electrical and mechanical link.

(2) Maximum consumption of all contactors controlled.

PB106120-34

DB123777

DB123316

PB106124-34

PB106123-34

DB123315

DB123778

DB123779