Table of Contents Table of Contents
Previous Page  492 / 576 Next Page
Information
Show Menu
Previous Page 492 / 576 Next Page
Page Background

492

PB502616-17

PB502625-21

PB502615-13

Characteristics

Side-mounting models

Floor-standingmodels

Cooling units for electrical control panels.

b

b

Alarm signal for door contact included in all models.

b

b

Eyebolts included.

b

b

Among best in class components.

b

b

The external filter, not included as standard, is strongly recommended for harsh environments.

Material

RAL 7035 grey painted zinc-coated steel or stainless steel

Certifications

b

b

CE declaration

b

b

UL (only references ending with UL)

Installation

Indoor

b

b

Indoor

b

b

Cannot be installed

with enclosures with

plinths

Cooling characteristics

Cooling power L35-L35

2000 W (6824 Btu/h) 2900 W (9895 Btu/h) 3850 W (13137 Btu/h) 5800 W (19790 Btu/h)

Cooling power L35-L50

1510 W (5152 Btu/h) 2250 W (7677 Btu/h) 2870 W (9793 Btu/h) 4350 W (14843 Btu/h)

Air flow of the internal circuit (enclosure)

860 m³/h

1450 m³/h

1450 m³/h

1450 m³/h

Air flow of the external circuit (ambient)

1050 m³/h

1450 m³/h

1450 m³/h

2900 m³/h

Thermostat type

Electronic

Electronic

Electronic

Electronic

Temperature setting range

+20 … +46°C

+20 … +46°C

+20 … +46°C

+20 … +46°C

Maximum outside temperature

+55°C (+45°C)

+55°C (+45°C)

+55°C (+45°C)

+50°C

Temperature range external circuit (ambient)

+20 … +50°C

(+20 … +45°C)*

+20 … +50°C

(+20 … +45°C)*

+20 … +50°C

(+20 … +45°C)*

+20 … +50°C

Type of cooling gas

R134a

R134a

R134a

R407c

Cooling gas weight

0.59 kg

0.84 kg

1.14 kg

1.8 kg

Maximum pressure cooling circuit

25 bar (28 bar)*

25 bar (28 bar)*

25 bar (28 bar)*

27 bar

External filter

Optional,

see page 505

Optional,

see page 505

Optional,

see page 505

Polyurethane filter

standard

Electric characteristics

Input voltage

3 x 400-460 V /

50-60 Hz*

3 x 400-460 V /

50-60 Hz*

3 x 400-460 V /

50-60 Hz*

3 x 400 V / 50 Hz

Starting / Rated Intensity

10 A / 2.5 A

14 A / 2.6 A

18 A / 3.6 A

21.7 A / 5.9 A

Power consumption absorved L35-L35

970 W

1220 W

1780 W

2340 W

Power consumption absorved L35-L50

1150 W

1440 W

2050 W

3880 W

Energy efficiency ratio (EER) L35-L35

2.1

2.4

2.2

2.5

Thermal protection recommended (fuse)

T6 A

T6 A

T8 A

T8 A

Physical characteristics

External dimensions (H x W x D)

999 x 405 x 237 mm 1270 x 500 x 336 mm 1270 x 500 x 336 mm 2000 x 600 x 380 mm

Protection degree IP internal /external

IP55 / IP34

IP55 / IP34

IP55 / IP34

IP54 / IP34

Noise level

65 dB

70 dB

70 dB

72 dB

Weight of unit

54 kg

84 kg

85 kg

150 kg

References

Steel

NSYCU2K3P4

NSYCU3K3P4

NSYCU4K3P4

NSYCU6K3P4

**

Stainless steel

NSYCUX2K3P4

NSYCUX3K3P4

NSYCUX4K3P4

-

Steel UL

NSYCU2K3P4UL NSYCU3K3P4UL NSYCU4K3P4UL

-

Stainless steel UL

NSYCUX2K3P4UL NSYCUX3K3P4UL NSYCUX4K3P4UL

-

* Certification UL only 60 Hz.

** Available from 2016.

ClimaSysCU

Thermal management system

Characteristics

Cooling units

New