Table of Contents Table of Contents
Previous Page  490 / 576 Next Page
Information
Show Menu
Previous Page 490 / 576 Next Page
Page Background

490

PB502617-21

PB502614-15

PB502613-13

PB502595-17

Characteristics

Side-mounting models

Cooling units for electrical control panels.

b

b

Respect for the environment by using environmentally friendly gas R134a (HFC).

b

b

Electronic thermostats in all models.

b

b

Alarm signal for door contact included in all models.

b

b

Eyebolts included.

b

b

Among best in class components.

b

b

The external filter, not included as standard, is strongly recommended for harsh environments.

b

b

HMI screen.

Material

RAL 7035 grey painted zinc-coated steel or stainless steel

Certifications

b

b

CE declaration

b

b

UL (only references ending with UL)

Installation

Indoor

Cooling characteristics

Cooling power L35-L35

300 W (1024 Btu/h)

380 W (1297 Btu/h)

640 W (2184 Btu/h)

820 W (2798 Btu/h)

Cooling power L35-L50

150 W (512 Btu/h)

240 W (819 Btu/h)

470 W (1604 Btu/h)

680 W (2320 Btu/h)

Air flow of the internal circuit (enclosure)

280 m³/h

280 m³/h

330 m³/h

330 m³/h

Air flow of the external circuit (ambient)

280 m³/h

280 m³/h

570 m³/h

570 m³/h

Thermostat type

Electronic

Electronic

Electronic

Electronic

Temperature setting range

+20 … +46°C

+20 … +46°C

+20 … +46°C

+20 … +46°C

Maximum outside temperature

+55°C

+55°C (+50°C)**

+55°C (+50°C)**

+55°C (+50°C)**

Temperature range external circuit (ambient)

+20 … +55°C*

+20 … +55°C*

(+20 … +50°C)**

+20 … +55°C*

(+20 … +50°C)**

+20 … +55°C*

(+20 … +50°C)**

Type of cooling gas

R134a

R134a

R134a

R134a

Cooling gas weight

0.13 kg

0.16 kg

0.23 kg

0.23 kg

Maximum pressure cooling circuit

25 bar

26 bar (28 bar)**

25 bar (28 bar)**

25 bar (28 bar)**

External filter

Optional,

see page 505

Optional,

see page 505

Optional,

see page 505

Optional,

see page 505

Electric characteristics

Input voltage

1 x 230 V / 50-60 Hz 1 x 230 V / 50-60 Hz** 1 x 230 V / 50-60 Hz** 1 x 230 V / 50-60 Hz**

Starting / Rated Intensity

4.2 A / 1.5 A

6.0 A / 1.6 A

8.1 A / 2.1 A

10.8 A / 2.6 A

Power consumption absorved L35-L35

270 W

280 W

400 W

440 W

Power consumption absorved L35-L50

310 W

330 W

470 W

490 W

Energy efficiency ratio (EER) L35-L35

1.1

1.4

1.6

1.9

Thermal protection recommended (fuse)

T4 A

T4 A

T6 A

T6 A

Physical characteristics

External dimensions (H x W x D)

340 x 525 x 135 mm 460 x 285 x 180 mm 606 x 316 x 212 mm 783 x 348 x 215 mm

Protection degree IP internal /external

IP55 / IP34

IP55 / IP34

IP55 / IP34

IP55 / IP34

Noise level

61 dB

60 dB

65 dB

65 dB

Weight of unit

17 kg

17 kg

21 kg

27 kg

References

Steel

NSYCU300H

NSYCU400

NSYCU600

NSYCU800

Stainless steel

-

NSYCUX400

NSYCUX600

NSYCUX800

Steel UL

-

NSYCU400UL

NSYCU600UL

NSYCU800UL

Stainless steel UL

-

-

NSYCUX600UL

NSYCUX800UL

* 50°C at 60 Hz.

** Certification UL only 60 Hz.

ClimaSysCU

Thermal management system

Characteristics

Cooling units

New