387

L ≤ 10 - 15 m

DB300007SE-40

DB300008SE-39

DB300010SE-60

DB300011SE-46

Spacial EMCsolution

Electromagnetic protected

steel enclosures

Introduction

Installation

According to the type of interference generated by the devices:

b

b

Low frequencies, "conducted interference" (up to 30 MHz),

b

b

High frequencies, "radiated interference" (higher than 1 MHz),

the rules to be taken into account relate to the choice of components that provide

the most economical solution to complete the installation.

Low-frequency interference

b

b

Importance of the protection systems:

v

v

filters, overvoltage suppressor, isolating transformer for the power supply,

v

v

cable length.

High-frequency interference

b

b

Importance of the installation method:

v

v

earth connections, cable length and section,

v

v

cable selection and rules, cable runs, connections,

v

v

enclosures and installation.

Specifics

Screen connections

It is recommended to earth screens at both ends. In addition, it is advisable to

increase the number of intermediate earth connections.

If the screen is only earthed at one end, there can be a considerable difference in

potential between the two ends. In addition, this screen will be ineffective against

external high-frequency interference.

Transformers

The transformer chassis must be mounted, metal to metal, on the reference potential

plate, that is, on a plain chassis supporting the equipment.

Cable runs

The metal ducts and conduits, when correctly connected, provide an extremely

effective second screen for the cables.

Cable ends must be screwed to the metal enclosures in order to provide an effective

connection.

Enclosures

The interfering and sensitive components, cables etc. should be installed in separate

enclosures or located at some distance from each other.

Note:

For further information, consult your local sales office or our educational leaflet entitled

"Electromagnetic compatibility".

Earth plate or

reference potential

sheet connected to

the chassis

Excellent

Soldered

Earth connection

by the screws

Metal ground plate or

reference potential sheet

Paint = INSULATION

Excellent

To the power

units

Mains

Actuators Sensors

Probes

Detectors,

etc.

Heating

Low level

Poor