![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0349.jpg)
349
SF
PB502637-25
PB502638-25
PB502639-30
PB502640-23
PB502638-25
PB502602-25
New
Spacial SF&S3D
Seismic and nuclear enclosures
Characteristics
Spacial SF 5G solutions for seismic risks
Characteristics
Spacial SF 5G cubicle reinforcement
If the following mounting parts are used in SF 5G cubicles:
b
b
Plain mounting plates;
b
b
Fixed 19" rack;
then it is mandatory to mount the corresponding reinforcing brackets, universal cross rails and heavy-load cross rails in order to
ensure the safety and optimal performance of the cubicle and the equipment it contains.
A&C configuration (H 2000 mm x W 800 mm x D 600 mm):
Mandatory components for reinforcing Spacial SF 5G cubicles with
plain mounting plate
19" configuration
(H 2000 mm x W 600 mm x D 800 mm):
Mandatory components for reinforcing Spacial
SF 5G cubicles with fixed 19" rack
Depth (mm)
Reinforcing bracket for
plain mounting plate
Universal cross rails Heavy-load cross rails Reinforcing bracket for
fixed 19" rack
Universal cross rails
600
NSY5GSPK
NSYSUCR9060
NSYHLCR60
-
-
800
-
-
-
NSY5GRCK42
NSYSUCR9080
Characteristics Nominal
dimensions (mm)
Load tested
(kg)
Plain door
Plain door
100 mm plinth Mounting
plate*
19" rack*
Two configurations were tested:
b
b
Control and automation configuration. 250 kg load uniformly distributed over the plain mounting plate at the rear.
b
b
Configuration with fixed 19" rack. 250 kg load distributed in accordance with a standard (FPR).
H W D
Without rack
Spacial SF 5G
A&C configuration 2000 800 600 250
NSYSF5G20860 NSY5G2SP206 NSYS5GPC86 NSYMP208
-
19" configuration
2000 600 800 250
NSYSF5G20680 NSY5G2SP208 NSYS5GPC86
-
NSYRCK42
* For plain mounting plate and 19" rack, see information on cubicle reinforcement.
NB:
The customer must ensure good cubicle/base connection.