Table of Contents Table of Contents
Previous Page  309 / 576 Next Page
Information
Show Menu
Previous Page 309 / 576 Next Page
Page Background

309

Spacial SFP

Prisma functional system

Power busbars

Linergy LGYE - Horizontal flat busbars up to 4000 A

Installation in Spacial SFP

Up to 1600 A

Up to 4000 A

Copper bar, 2000 mm length

Permissible current for an ambient temp.

of 35 °C around the switchboard

IP

y

31 800 A 1000 A 1400 A 1800 A 1800 A 2050 A 2300 A 2820 A

3300 A

3760 A

IP > 31 750 A 900 A 1250 A 1600 A 1600 A 1850 A 2000 A 2500 A

2900 A

3340 A

Busbar cross-section (mm)

60 x 5 80 x 5 60 x 5 80 x 5 80 x 10 50 x 10 60 x 10 80 x 10

100 x 10

120 x 10

Number of busbars per phase

1

1

2

2

1

2

2

2

2

2

Total number of vertical modules (50 mm)

3

4

Cat. no.

04536 04538 04536 04538 04548 04545 04546 04548

04550

04552

Busbar supports

DD385403.eps

DD381226-LIN-15.eps

Fixed support

04664

DD381225-LIN-15.eps

Free support

04662

In cubicle:

W700 with

75 mm distance

between bars

Characteristics

2 fixed supports for Spacial SFP 700 wide frame are compulsory.

1 fixed support for 300/400 wide frame are compulsory.

If more supports are needed, add free supports.

Number of

supports

depending on Icw

(kA rms/1 s)

y

15

2

y

25

2+1 2

y

30

2+1

2

y

40

2+1

2

y

50

-

2+1

2

y

60

-

2+1

y

65

-

2+1

y

75

-

2+2

2+1

y

85

-

-

2+1

Cat. no.

Fixed support

04664

04664

04664

+

04671

Free support

04662

04662

04662

+

04671

In duct:

W300 with

75 mm distance

between bars

Number

depending on Icw

(kA rms/1 s)

y

30

1

y

50

1+1

1

y

85

-

2

Cat. no.

depending on

depth

Fixed support

NSYBHS500

(D500)

or

NSYBHS600

(D600)

or

NSYBHS800

(D800)

NSYBHS500

(D500)

or

NSYBHS600

(D600)

or

NSYBHS800

(D800)

NSYBHS500

(D500)

or

NSYBHS600

(D600)

or

NSYBHS800

(D800)

+

04671

Free support

04662

04662

04662

+

04671

In cubicle

W700 with

115 mm distance

between bars

Number

depending on Icw

(kA rms/1 s)

y

30

-

2

y

40

2+1

2

y

60

2+1

y

75

2+2

2+1

y

85

-

2+2

2+1

Cat. no.

Fixed support

NSYBHS800L

NSYBHS800L

+

04671

Free support

04678

04678

+

04671

In duct

W300 with

115 mm distance

between bars

Number

depending on Icw

y

50

-

1

y

85

2

Cat. no.

Fixed support

NSYBHS800L

NSYBHS800L

+

04671

Free support

04678

04678

+

04671

Joints

Installation in Spacial SFP

Up to 1600 A

Up to 4000 A

1 vertical bar

per phase

2 vertical bars

per phase

1 vert. bar

per phase

2 vertical bars per phase

Busbar cross-section (mm)

60 x 5 80 x 5 60 x 5 80 x 5 80 x 10 50 x 10 60 x 10 80 x 10

100 x 10

120 x 10

Sliding joints with self-breaking lock nut

04640

04641

DD385385.eps

DD385386.eps

DD385358.eps

Cat. no.

04640 04641 04640 04641 04641 04640 04640 04641

04641

04643

Note:

When installed at the bottom of a cubicle, the busbar must be partitioned.