Table of Contents Table of Contents
Previous Page  198 / 210 Next Page
Information
Show Menu
Previous Page 198 / 210 Next Page
Page Background

198

Conform to BS EN 60309-1, BS EN 60309-2, IEC 60309-1 and IEC 60309-2

n

Voltage identification

Colours specified by standards and the clock indexing of the contact tubes in socket outlets

n

With Legrand Hypra and P17 Tempra industrial plugs and sockets, your installations will comply fully with international

standards :

• Standard IEC 60309-1 : this defines the safety regulations (protection of workers) which should be observed in the manufacture of industrial power

sockets and plugs

• Standard IEC 60309-2 : this defines the interchangeability regulations for the dimensions of equipment with pins and sockets

These safety regulations, together with the requirements of standard BS EN 60309-1, define the safety conditions necessary for normal operation.

It is prudent to go one step further and insist on equipment which ensures the safety of the persons as a priority as well as ease of operation.

Many manufacturers therefore use sockets which incorporate a switch, to avoid on-load disconnection (eg : Hypra Prisinter).

2 P

20 to 25 V

±

3 P

no minor

keyway

major keyway

42 V

±

50 – 60 Hz White

24 V

±

50 – 60 Hz Violet

ELV by position of the minor keyway

42 V

=

White

20 to 25 V and 40 to 50 V D.C.

minor keyway

at 10 h

major keyway

2 P

3 P

minor keyway

at 12 h

major keyway

40 to 50 V

±

110 V

±

50 – 60 Hz Yellow

LV by the position of the earth contact tube in relation to the major keyway in the socket outlets

230 V

±

50 – 60 Hz Blue

400 V

±

50 – 60 Hz Red

2 P + E

110 to 130 V

4h

3 P + E

100 to 130 V

keyway

4h

3 P + N + E

57/100 to 75/130 V

4h

earth contact tube

110 to 130 V

±

2 P + E

200 to 250 V

6h

3 P + E

200 to 250 V

keyway

9h

3 P + N + E

120/208 to 144/250 V

9h

200 to 250 V

±

2 P + E

380 to 415 V

9h

3 P + E

380 to 415 V

keyway

6h

3 P + N + E

200/340 to 240/415 V

6h

380 to 415 V

±

> 50 to 500 V

±

100 to 300 Hz inclusive Green

3 P + E

keyway

10h

earth

contact tube

500 V

±

50 – 60 Hz Black

3 P + E

keyway

7h

earth

contact tube

n

Terminal connection capacity, Prisinter rating and contact sizes

• Diameters of pins or contact tubes (mm)

• Terminal connection capacity

(A) Panel mounting sockets

(B) Mobile sockets and plugs

16 A

32 A

63 A 125 A

24 V

±

42 V

±

Phase

6

6

42 V

=

Phase +

Neutral

5

6

8

10

110 V

±

230 V

±

400 V

±

Earth

7

8

10

12

440 V

±

500 V

±

Pilot

6

6

Hypra/P 17 Tempra

ELV 16/32 A

1 x 10 mm (A + B)

LV 16 A

1 x 4 mm (A)

1 x 2·5 mm (B)

LV 32 A

1 x 10 mm (A)

1 x 6 mm (B)

LV 63 A

1 x 25 mm (A)

1 x 16 mm (B)

LV 125 A

1 x 70 mm (A)

1 x 50 mm (B)

• Hypra Prisinter breaking capacity

for 3 x 400 V

±

according to IEC 60947-1-3

Category

16 A

32 A

63 A

AC 1

16 A

32 A

63 A

AC 23

8·4 kW

16 . 8 kW

33 kW

AC 3

8·4 kW

16 . 8 kW

33 kW

industrial plugs and sockets to International Standards