![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0112.jpg)
110
Conform to EN 60730-1 and EN 60730-2-7
Supply voltage : 230 V
±
50/60 Hz
Accuracy : ±1 second per day
LCD digital display
Programmable for 1 minute minimum at 1 minute intervals
Panel and DIN rail
4
mounting :
- can be panel mounted using Cat. No. 0498 32
- can be clipped to DIN rail
4
using Cat. No. 0044 09
Pack
Cat. Nos.
MaxiRex D Plus
Working reserve : 6 years
Programmable for 1 minute min. at 1 minute steps
either as 24 hour/7 day using pre-set groups of days
One programme consists of 1 “ON” and 1 “OFF”
time and the allocation of any day of the week or a
combination of days. Plus the selected channel
Example :
Prog. 1 On 07.00hrs Off 08.15hrs Mon-Fri Ch1
Prog. 2 On 16.00hrs Off 20.15hrs Mon-Fri Ch2
Prog. 3 On 10.00hrs Off 16.15hrs Sat-Sun Ch1
Additional features :
EEPROM memory stores programme indefinitely
Optional automatic summer/winter time change
Manual override (ON or OFF)
Automatic advance (changes contact position until
next automatic ON time)
MaxiRex D72/1 Plus
1
0496 80
24 hour or 7 day
28 programme
1 channel
1 x 16 A voltage free c/o contact
MaxiRex D72/2 Plus
1
0496 82
24 hour or 7 day
2 x 14 programme
2 channel
2 x 8 A voltage free c/o contacts
Fixing accessories
5
0498 32 Clip-on support frame for panel mounting
5
0044 09 DIN rail
4
adaptor
0496 82
L
11 14
22 24 21
12
N
U
1
U
2
M
~
049681
1 4 2
U
1
U
2
M
~
049681
11 14 12
22 24 21
MaxiRex D72/2 Plus
MaxiRex D72/1 Plus
n
Wiring diagrams
n
Mounting options
MaxiRex D72/2 Plus
E 049750 b
Panel mounting
with support Cat. No. 0498 32
to be ordered separately
0044 09
Clipped on to DIN rail
EN 60715
2
Adaptor to be ordered
separately (Cat. No. 0044 09)
0498 32
n
Technical information
Type
MaxiRex D72/1 Plus
MaxiRex D72/2 Plus
Cat. No.
0496 80
0496 82
Programme
24 hour or 7 day
No. of channels
1
2
No. of ON-OFF
28
2 x 14
actions per day
Switching
capacity :
cos
ϕ
= 1
16 A
8 A
incandescent lamp
5 A
3 . 5 A
cos
ϕ
= 0·6
8 A
4 A
Contact
1 changeover
2 changeover
switch
switches
Min. prog. time
1 minute
Switching step
1 minute
Accuracy
±1 second per day
Working reserve
1
6 years
Programme
memory
EEPROM
Manual switching
Override and permanent
Operating temp.
–20 °C to +55 °C
Storage temp.
–20 °C to +60 °C
Weight
178 g
204 g
1 : For time and date only
72
69
110
R max. 25
44
34
66 4
66
-0·3
n
Dimensions (mm)
Panel cut out required
MaxiRex digital time switches
surface or 72 x 72 mm panel mounting