Background Image
Table of Contents Table of Contents
Previous Page  40 / 132 Next Page
Information
Show Menu
Previous Page 40 / 132 Next Page
Page Background

40

MR tap-off boxes :

plug-in type 32-630 A

MR tap-off boxes from 10 to 1 000 A can accomodate different protection devices, including fuses, MCBs or MCCBs. Can be operated when

energised and under load conditions up to a rating of 32 A due to the integration of an isolating device within the cover. All insulating plastic

components comply with the incandescent wire test (EN 60695-2-1) and have a V2 self extinguishing degree (UL94). Standard degree of protection is

IP 55 without using additional protection kits. For dimensions, technical information and mounting instructions

see p. 47-48

Plug-in tap-offs with fuse carriers (or empty) 63-400 A

TYPE 3

Cat. Nos.

Weight

(kg)

Fuse

Carrier

TYPE 4

TYPE 5

55655051

0·85

CH10

(Ø10·3 x 38)

32 A

55055062

3·2

TIA / TIS

63 A

55055063

3·3

TCP

100 A

55055055

2·9

Empty

125 A

55055053

3·35

NH 0

55055057

3·35

NH 00

50404004

3·6

NH 0

160 A

55655057

14·9

NH 1

250 A

55655059

14·3

Empty

400 A

(Neutral section 50%)

55655058

15·8

NH 1

Rating

Plug-in heavy duty metal tap-offs 63-630 A

TYPE 8

TYPE 7

TYPE 6

These PE + FE tap-off boxes

have separate terminals for

the two parallel earths

(casing and conductor)

PE = protection earth

FE = functional earth

63 A

125 A

Rating

160 A

250 A

400 A

630 A

Cat. Nos.

Weight

(kg)

Cat. Nos.

Weight (kg)

Cat. Nos.

Weight (kg)

Empty version

With fuse holder

With switch

disconnector and

fuseholder (AC23)

50414001

8·60

50414021

CH22 (Ø22 x 58)

8·75

50411601

NH 00

9·50

50414002

8·80

50414022

NH 00

8·90

50411622

NH 00

9·70

50414003

8·80

50414023

NH 00

9·10

50411623

NH 0

9·70

50414004

23

50414026

NH 2

33

50414024

NH 2

25

50411624

NH 1

30

50411625

NH 2

38

50414005

25

50414025

NH 3

33

50411646

NH 3

38

250A

400A - 630A

63A - 125A - 160A

250A

400A - 630A

63A - 125A

250A

400A - 630A

63A - 125A - 160A

Plug-in tap-offs fitted with DIN rail and transparent hinged window 63-400 A

TYPE 4

TYPE 5

Rating

Cat. Nos.

Weight

(kg)

Cat. Nos.

Weight

(kg)

Cat. Nos.

Weight

(kg)

Cat. Nos.

Weight

(kg)

4 mod. DIN rail

8 mod. DIN rail

8 mod. DIN rail

11 mod. DIN rail

7 mod. DIN rail

11 + 11 mod. DIN rail

Can fit some MCCBs

Not suitable for MCCBs

55055086

3·2

55055088

3·6

63 A

125 A

160 A

400 A

55055066

3·0

55055077

3·0

55055056

3·2

55055068

3·6

50404024

3·6

55055070

13·4

55055071

15·3

For dimensions, technical information and mounting instructions see p. 47-48