Example of
a page title
42
klik • Technical
klik 7 in
Lighting Control Module Functions (via the KlikLink App)
LCM Functions (via the KlikLink App)
Lighting Configuration Profiles.
The KLCM KlikLink App can be is pre-loaded with the most common
room type configuration profiles. These are selected in the File
Manager section of the KlikLink App and are provided to speed up
the LCM set-up.
Switching - On/Off.
Each channel is capable of being switched via one of 4 switch inputs.
This is an on/ off state utilised for standard luminaires.
Presence and Absence Sensing.
Each output channel can be set to Presence or Absence and can be
different on each channel. Absence detection will give the best energy
efficiencies by minimising unwanted activations, whilst Presence
gives an immediate response to occupation in an area.
Sensor with integral lux sensor.
This allows daylight dimming and switch utilising any natural light
available
Dimming – DSI, DALI (Broadcast).
The LCM takes information from the sensor and broadcasts a
signal on the required channel to all connected luminaires and can
be controlled via a retractive wall switch or utilising the daylight
dimming function. The protocol for this broadcast is selected during
programming.
Scene Setting.
4 lighting scenes are possible (plus global Up/Down-On/Off) and can
be achieved with via centre off 2 pole retractive grid switch modules
(3 grid modules to control all inputs) The LCM can be configured
during programming to have 2 separate Scene profiles.
Partition Switch Function.
This allows the control of a room with a partition and switch fitted. If a
partitioned room has individual wall switches controlling each section,
when the partition is removed, both sets of switches could control the
whole area. This can be used in conjunction with profiles.
Corridor Hold Function.
This is achieved by linking a series of LCMs together with an RJ45
lead and assigning certain channels with the attributes of a corridor.
If there is any area occupied, the associated corridor lighting will be
held ON.
Variable burn in up to 250 hrs.
Allows dimmable luminaires to be set at 100% output for the required
burn in time period (Dimming is disabled during this period) This may
be beneficial to the life of the lamps. After the burn in time, the LCM
will return to any programmes set (e.g. dimming)
Integral Emergency Test Timers.
This allows the emergency test to be carried out via an emergency
test switch. The timers can be set for up to 5 hours within the App.
Whilst on test the other luminaires will dim to a pre-set value.
Light Level Offset between Channels.
This function allows the levels from different channels to set as a
percentage of the lead channel. For example when a number of
different dimming levels are set within an area as a scene set, the
lighting levels can be adjusted universally across all channels, whilst
maintaining the relationship between channels.
3 Level Timeout.
Allows the lighting to turn Off or Down in three stages. When no
presence has been detected for the timeout period, the lighting can
be turned down to the first set level, after a further period the lighting
can be reduced further, after the final time period the luminaires can
be turned off or driven to a minimum value set during programming.