klik • Technical

klik 7 in

IR commissioning remote control (EEK001)

Settings available

Key

Meaning

Indication

Function

Presence

Green LED on

Presence on (automation mode)

Absence

Red LED on

Absence on (semi automatic mode)

Power Up

Green LED on

The light is automatically switched on for 30

seconds after power up

Red LED on

During warm up phase, the light output is off

Reset

LED on

To return to factory settings (Lux = 400, time

= 20 min, presence on, power up off and cell

active)

Test

LED on

To validate the detection area

Time

LED on

To set the time

It is possible to add times together e.g. press

2’ and 5’ for a time value of 7’

Day level

1000 Lux

LED on

To set the value to 1000 Lux

Learn

LED on

To learn the current Lux level

Corridor

200 Lux

LED on

To set the value to 200 Lux

Office

400 Lux

LED on

To set the value to 400 Lux

Lux +

LED on

To increase the Lux level (+100)

Lux -

LED on

To decrease the Lux level (-100)

Active cell

Green LED on

The light is continuously measured

Passive cell

RED LED on

The sensor will not switch the light off even if

the ambient luminosity is sufficient

Memo and set Key Meaning

Indication

Function

Press

LED is on until a setting is changed To load/unload Memo 1

Long press

LED is on for 5s, then will blink until

released. After release, the LED goes

off in case of setting change

To save the current setting as Memo 1

Press

LED is on until a setting is changed To load/unload Memo 2

Long press

LED is on for 5s, then will blink until

released. After release, the LED goes

off in case of setting change

To save the current setting as Memo 2

Short press (<5s)

LED flashes

To send an IR message of the current setting

Long press (>5s but <10s)

only available if no setting

active

LED blinks until release press

To toggle automatic mode on DALI/DSI

Use

The remote control allows the user to set or

modify presence detector settings. When the

potentiometer is on auto test it allows single

and multiple settings.

The SET key is used to send the IR messages

to the occupancy sensors. Multiple settings

can be stored in Memo 1 and Memo 2 and

re-called to set several devices.

Single setting

Example: reset

Multiple settings

Define the parameters to be changed and

press SET to send.

Example: for 25 minutes and corridor use,

press 20’, 5’ and corridor.

In the case of 2 opposite states the green LED

denotes ON and red LED denotes OFF (except

Presence / Absence).

When no function is selected all LED’s are OFF.

Technical specification

Power supply:1x 3V CR2032

Shelf life of battery: 2½ years

Protection index: IP 30

LED

The acknowledgment

LED blinks during

the sending of the IR

message.

+

+

+

+