37
Hager Sales • 01952 675612 Technical Service Centre • 01952 675689
klik 7 pin
Occupancy Sensors
EEK513P / EEK515P
EEK523P / EEK525P
KLCM-OS
Detection range
motion area: diameter 7m (product installed at 2½m height)
presence area: diameter 5m (product installed at 2½m height)
motion area: diameter 6m (product
installed at 2½m height)
presence area: diameter 6m
(product installed at 2½m height)
Supply voltage
230 V AC + 10% -15%
12V DC
Frequency
50/60 Hz
Local lux threshold setting 5 to 1000 lux
3 modes available
0 - 4000 Lux
Local time setting
1 min to 1hr
Via KLCM
Commissioning via
installer remote control
EEK001 for power up, absence / presence mode, timer active / passive
cell
KlikLink App
Control with IR user
remote control
EEK002 for ON / OFF override
EEK002 for ON / OFF override and
dimming up / down
KlikLink App
Output
16A AC1 relay output (cut live):
- 2300W incandescent or 230V
halogen:
> 26000 cycles
- 1500W VLV halogen lamps
with ferromagnetic or electronic
transformer:
> 35000 cycles
- 1000W / 130 μF parallel
compensated fluo tube: > 50000
cycles
-23 x 23W fluo-compact with
electronic ballast: > 20000 cycles
14V / 50mA (for a DALI bus with 24
ballasts)
- No isolation between the mains
and the DALI bus
RS485
Push button input
phase input for absence / presence
detection (semi-automatic /
automatic mode)
same phase as power supply.
to dim up / down and absence
/ presence detection (semi-
automatic / automatic mode) same
phase as power supply.
N/A
Terminals
for 1.5mm
2
rigid / flexable wires
RJ11
Power dissipation
300mW
60mW
3mA @ 12V DC
Isolation class
II
Protection
IP41 / IK03
Operating temperature -10ºC to +45ºC
-20C to +60C
Storage temperature
-20ºC to +60ºC
-2-C to +70C
Standards
IEC 60669-1, IEC 60669-2-1
BS EN55015:2013
Technical Characteristics
h
x
y
D
S
5m
1m
2.5m
2.5m
auto
test
1min
1h
20min
1
on
2
lux
t
H 2.5m 3m 3.5m
X
5m 5m 5m
Y 7m 8m 9m
Detection areas
Settings EEK513P/EEK515P
EEK523P/EEK525P
Mounting
ceiling
protective cover
cable clamp
10 < t < 28mm
Technical