28
klik • Technical
klik 4 pin
IR commissioning remote control (EEK001)
Settings available
Key
Meaning
Indication
Function
Presence
Green LED on
Presence on (automation mode)
Absence
Red LED on
Absence on (semi automatic mode)
Power Up
Green LED on
The light is automatically switched on for 30
seconds after power up
Red LED on
During warm up phase, the light output is off
Reset
LED on
To return to factory settings (Lux = 400, time
= 20 min, presence on, power up off and cell
active)
Test
LED on
To validate the detection area
Time
LED on
To set the time
It is possible to add times together e.g. press
2’ and 5’ for a time value of 7’
Day level
1000 Lux
LED on
To set the value to 1000 Lux
Learn
LED on
To learn the current Lux level
Corridor
200 Lux
LED on
To set the value to 200 Lux
Office
400 Lux
LED on
To set the value to 400 Lux
Lux +
LED on
To increase the Lux level (+100)
Lux -
LED on
To decrease the Lux level (-100)
Active cell
Green LED on
The light is continuously measured
Passive cell
RED LED on
The sensor will not switch the light off even if
the ambient luminosity is sufficient
Memo and set Key Meaning
Indication
Function
Press
LED is on until a setting is changed To load/unload Memo 1
Long press
LED is on for 5s, then will blink until
released. After release, the LED goes
off in case of setting change
To save the current setting as Memo 1
Press
LED is on until a setting is changed To load/unload Memo 2
Long press
LED is on for 5s, then will blink until
released. After release, the LED goes
off in case of setting change
To save the current setting as Memo 2
Short press (<5s)
LED flashes
To send an IR message of the current setting
Long press (>5s but <10s)
only available if no setting
active
LED blinks until release press
To toggle automatic mode on DALI/DSI
Use
The remote control allows the user to set or
modify presence detector settings. When the
potentiometer is on auto test it allows single
and multiple settings.
The SET key is used to send the IR messages
to the occupancy sensors. Multiple settings
can be stored in Memo 1 and Memo 2 and re-
called to set several devices.
Single setting
Example: reset
Multiple settings
Define the parameters to be changed and
press SET to send.
Example: for 25 minutes and corridor use,
press 20’, 5’ and corridor.
In the case of 2 opposite states the green LED
denotes ON and red LED denotes OFF (except
Presence / Absence).
When no function is selected all LED’s are OFF.
Technical specification
Power supply:1x 3V CR2032
Shelf life of battery: 2½ years
Protection index: IP 30
LED
The acknowledgment
LED blinks during
the sending of the IR
message.
+
+
+
+