Hager Sales • 01952 675612   Technical Service Centre • 01952 675689

Technical Characteristics

EEK513W / EEK515W

Detection range

motion area: diameter 7m (product installed at 2½m height)

presence area: diameter 5m (product installed at 2½m height)

Supply voltage

230 V AC + 10% -15%

Frequency

50/60 Hz

Local lux threshold setting

5 to 1000 lux

Local time setting

1 min to 1hr

Commissioning via installer remote control

EEK001 for power up, absence / presence mode, timer active / passive cell

Control with IR user remote control

EEK002 for ON / OFF override

Output

16A AC1 relay output (cut live):

- 2300W incandescent or 230V halogen:

> 26000 cycles

- 1500W VLV halogen lamps with ferromagnetic or electronic transformer:

> 35000 cycles

- 1000W / 130 μF parallel compensated fluo tube: > 50000 cycles

-23 x 23W fluo-compact with electronic ballast: > 20000 cycles

Push button input

phase input for absence / presence detection (semi-automatic / automatic mode)

same phase as power supply.

Terminals

for 1.5mm

2

rigid / flexible wires

Power dissipation

300mW

Isolation class

II

Protection

IP41 / IK03

Operating temperature

-10ºC to +45ºC

Storage temperature

-20ºC to +60ºC

Standards

IEC 60669-1, IEC 60669-2-1

t

N

L

1

L N PB

Push

button

L

230 V

M

N

L

1

L N PB

Push

button

L

230 V

M

Mounting

ceiling

protective cover

cable clamp

Wiring diagram

EEK510B (no cable supplied)

EEK513W (Cable supplied

connected to OS)

10 < t < 28mm

klik 4 in

Occupancy Sensors

h

x

y

D

S

5m

1m

2.5m

2.5m

auto

test

1min

1h

20min

1

on

2

lux

H 2.5m 3m 3.5m

X

5m 5m 5m

Y 7m 8m 9m

Detection areas

Settings

EEK513W/EEK515W

Technical