Table of Contents Table of Contents
Previous Page  167 / 430 Next Page
Information
Show Menu
Previous Page 167 / 430 Next Page
Page Background

4.45

Sales Service Centre • 01952 675612 Technical Support Helpline • 01952 675689

Transformer/Motor Protection

3 Phase 400V DOL Starting

Recommended Circuit Breaker

kW hp

FLC A (A) NBN (A) NCN (A)

NDN

HRC

Fuse (A)

0.18 0.25 0.87 -

2

-

4

0.25 0.33 1.17 -

3

-

4

0.37 0.5

1.2

-

3

-

4

0.55 0.75 1.8

-

4

-

6

0.75 1.0

2.0

10

6

6

6

1.1

1.5

2.6

16

10

6

10

1.5

2.0

3.5

16

10

10

16

2.2

3.0

4.4

20

16

16

16

3.0

4.0

6.3

25

20

20

20

4.0

5.5

8.2

32

25

25

25

5.5

7.5

11.2 50

40

40

32

7.5

10

14.4 63

50

50

40

11

15

21

-

-

-

63

15

20

27

-

-

-

80

18.5 25

32

-

-

-

80

22

30

38

-

-

-

80

30

40

51

-

-

-

100

37

50

63

-

-

-

125

45

60

76

-

-

-

125

55

75

91

-

-

-

160

75

100 124 -

-

-

200

90

125 154 -

-

-

250

110 150 183 -

-

-

315

132 175 219 -

-

-

355

150 200 240 -

-

-

355

160 220 257 -

-

-

355

Protection