Guide to commercial installations | Part 2 Panelboard: Standards and Regulations

11

If there is a three-line 16kA prospective fault current at the

panelboard, then you need to select single pole devices with

a minimum fault current rating of 8kA. This assumes that the

line to neutral prospective fault current is equal to or higher

than the prospective earth fault current.

The manufacturer is responsible for ensuring the capability of

the equipment between the incoming and the outgoing

terminals of the panelboard. This includes busbars and

connections as well as incoming and outgoing devices.

Therefore, the fault current rating is declared for each

panelboard as an assembly in accordance with

BS EN 61439-2, and is not just selected on the short circuit

ratings of the circuit breakers that are employed.

The terminology to define the short-circuit rating of a

panelboard is given in BS EN 61439 as follows:

• Rated short-time withstand current

I

cw

• Rated peak withstand current

I

pk

• Rated conditional short-circuit current

I

cc