Guide to commercial installations | Part 2 Panelboard: Standards and Regulations

15

To achieve the accuracy of a meter that requires the use of

CT’s, the cable resistance should not exceed a certain value

depending on the power capability of the CT.

The table below gives minimum CSA and maximum lengths.

CT

Max distance from

CT to meter (m)

Minimum cable

size (mm

2

)

SR051

2

1.5

5

4

SR101

2

1

5

2.5

10

4

SR200

2

1.5

5

2.5

SR250

2

1.5

5

2.5

SR300

5

1

10

1.5

SR400

10

1

SR600

10