Guide to commercial installations | Part 2 Panelboard: Standards and Regulations

9

Specifiers must follow the requirements for switching neutral; these are shown in the table below:

Isolation requirements of the neutral conductor

Main switch at origin of installation

Outgoing device at the origin and devices

within the installation

Use by Ordinary persons

Use by Skilled or

Instructed persons

Use by Ordinary persons

Use by Skilled or

Instructed persons

System

Single

Phase

Three

Phase

Single

Phase

Three

Phase

Single

Phase

Three

Phase

Single

Phase

Three

Phase

TN-S

TN-C S

YES

NO*

NO*

NO*

NO*

NO*

NO*

NO*

TT

YES

YES

YES

YES

YES

YES

YES

YES

Notes

* Provision shall be made for disconnecting the neutral conductor e.g. a suitable terminal or bolted link

BS 7671 also requires that the device used for isolation is designed and/or installed to prevent unintentional or inadvertent

closure. You can normally achieve this by fitting a locking mechanism to the device.

IEE Guidance Note 2 provides more detailed guidance on isolation and switching.