Use by skilled or instructed persons?

Where there are larger fault currents you should also consider the

type of person who will operate the devices.

If you can restrict access to the board to ‘skilled’ or ‘instructed’

persons only, perhaps by having the board in a locked riser or

ensuring that the door to the board is locked, then

BS EN 60947-2 can apply if the device has 947-2 ratings

assigned by the manufacturer.

In such a case the 10kA BS EN 60898 devices may be rated to

15kA; again manufacturer’s information must be obtained.

Distribution board fault current rating

The manufacturer is responsible for ensuring the capability of the

equipment between the incoming and the outgoing terminals of

the distribution board, which includes busbars and connections

as well as incoming and outgoing devices.

The manufacturer will have determined the distribution board

fault current rating(s), in accordance with the product standard.