Table 53.2 identifies that circuit breakers to BS EN 60947-2

are suitable for isolation. These are commonly used as outgoing

devices in distribution boards and can be used as isolation

devices for individual circuits.

The table below gives guidance as to whether the neutral

conductor needs to be switched or not.

Table 53.2

BS 7671 also requires that the device used for isolation is

designed and/or installed so as to prevent unintentional or

inadvertent closure. Usually this means that you need to fit some

kind of locking mechanism to the device.

IEE Guidance Note 2 gives more detailed guidance on isolation

and switching.

Isolation requirements of Neutral Conductor

Origin

Downstream

Use by

ordinary

persons

Use by skilled

or instructed

persons

Use by

ordinary

persons

Use by skilled

or instructed

persons

SP TP SP TP SP TP SP TP

TN YES NO* NO* NO*

NO NO NO NO

TT YES YES YES YES YES YES YES YES

Note* There should be some means of disconnecting the neutral by means of a bolted link