Data is subject to errors and technical modifications.
1.36
RCCBs
RCCB Auxiliaries
RCCB Auxiliaries
Auxiliary Interface
-
-
Indicates the position of the associated RCCB on, off or tripped. Also acts as RCCB interface with standard MCB auxiliaries
MZ203
-
MZ206
.
Shunt Trip
-
-
Allows remote tripping of the associated device, operation of the coil is indicated by a flag on the front of the device.
Under Voltage Release
-
-
Allows RCCB to be closed, only when voltage is above 85% of U n . RCCB will automatically trip when voltage falls to
between 70-35% of U n (230V). Operation of the release is indicated by a flag on the front of the device.
Description
Width
(1 Mod = 17.5mm)
Cat ref.
Auxiliary Interface
2 Normally Open / 2 Normally Closed 6A a.c.1 230V
1 Mod
CZ001
MZ203 CZ001
RCCB
to
MZ206
CZ001
MZ203
Description
Width
(1 Mod = 17.5mm)
Cat ref.
Auxiliary Contacts 5A - 230V a.c.
1NO +1NC Allows remote indication of main contact status
½ Mod
MZ201
Auxiliary Contacts & Alarm Induction
Allows indication of MCB status when turned off or tripped
½ Mod
MZ202
Shunt Trip
230V - 415V a.c.
110V - 130V d.c.
1 Mod
MZ203
24 - 48V a.c.
12 - 48V d.c.
1 Mod
MZ204
Under Voltage Release
230V a.c.
1 Mod
MZ206
48V d.c.
1 Mod
MZ205
Auxiliaries for MCBs & RCCBs
Characteristics
-
-
All auxiliaries are common to both single and multi-pole 10kA circuit breakers and RCCBs.
Connection capacity
-
-
4mm² flexible, 6mm² rigid
Shunt Trip:
Allows remote tripping of devices. Operation of the coil is indicated by a flag on the front of the device.
Under Voltage Release:
Allows MCB to be closed only when voltage is above 85% of U n . MCB will automatically trip when
voltage falls to between 70-35% of U n . Operation of the coil is indicated by a flag on the front of the device.
MZ203
to +
MZ201
+
MZ201
+
MZ202
+ MCB
MZ206 MZ201 MZ201 MZ201
MZ201
MZ202
MZ204
Commercial
Distribution