Data is subject to errors and technical modifications.
1.34
RCBOs
Single Pole & Switched Neutral
Characteristics
-
-
Compact protection devices which provide MCB overcurrent protection and RCCB earth fault protection in a single unit.
-
-
The device switches both the line and neutral conductors. All ratings have 30mA earth fault protection. The units feature
indicators which show whether a trip is due to an overcurrent or earth fault.
Technical Data
-
-
Breaking capacity: 4.5kA.
-
-
Conforms to EN 61009-1.
-
-
Operating Voltage: 230V a.c. -15% +10% 50Hz.
-
-
Mechanical life: 20,000 operations.
-
-
Connection Capacity: Rigid conductor 25mm², Flexible conductor 16mm²
-
-
Note:
Not for use in fixed busbar consumer units or distribution boards.
Current rating
Width
(1 Mod = 17.5mm)
C Curve
Cat ref.
6A RCBO SPSN 4.5kA
2 Mod
ADC806F
10A RCBO SPSN 4.5kA
2 Mod
ADC810F
16A RCBO SPSN 4.5kA
2 Mod
ADC816F
20A RCBO SPSN 4.5kA
2 Mod
ADC820F
25A RCBO SPSN 4.5kA
2 Mod
ADC825F
32A RCBO SPSN 4.5kA
2 Mod
ADC832F
Current rating
Width
(1 Mod = 17.5mm)
B Curve
Cat ref.
C Curve
Cat ref.
6A RCBO SPSN 6kA
2 Mod
ADA906U
ADA956U
10A RCBO SPSN 6kA
2 Mod
ADA910U
ADA960U
16A RCBO SPSN 6kA
2 Mod
ADA916U
ADA966U
20A RCBO SPSN 6kA
2 Mod
ADA920U
ADA970U
25A RCBO SPSN 6kA
2 Mod
ADA925U
ADA975U
32A RCBO SPSN 6kA
2 Mod
ADA932U
ADA982U
40A RCBO SPSN 6kA
2 Mod
ADA940U
ADA990U
RCBOs - Single Pole & Switched Neutral - 4.5kA C Curve
RCBOs - Single Pole & Switched Neutral - 6kA B & C Curve
ADA990U
ADC816F
Characteristics
-
-
Compact protection devices which provide MCB overcurrent protection and RCCB earth fault protection in a single unit.
-
-
The device switches both the line and neutral conductors. All ratings have 30mA earth fault protection. The units feature
indicators which show whether tripping is due to an overcurrent or earth fault.
Technical Data
-
-
Breaking capacity: 6kA.
-
-
Conforms to EN 61009-1.
-
-
Operating Voltage: 230V a.c. +10%/-15% 50Hz.
-
-
Mechanical life: 20,000 operations.
-
-
Connection Capacity: Rigid conductor 25mm², Flexible conductor 16mm²
-
-
Neutral connection flying lead - 700mm.
Triple Pole RCD Add-On Blocks for MCB Devices
Sensitivity
l ∆n
I n A
Width (35mm)
Cat ref.
30mA
63A
4 Mod
BD163T
100mA
63A
4 Mod
BE163T
300mA
63A
4 Mod
BF163T
Characteristics
-
-
Compatible with
NBN, NCN & NDN
range of MCB devices.
-
-
Can be used in combination with any Hager 3 pole 10kA MCB up to 63A. Requires the use of the adjacent outgoing way.
-
-
Type A RCD provides added protection against ‘pulsating d.c. current’
-
-
3 Phase earth leakage protection up to 63A.
-
-
One module add-on block + MCB combinations suit all Hager distribution boards.
-
-
BS EN 61009-1 Appendix G.
-
-
For technical details see page