DeskPod™

technical hotline +44 (0)1268 563720

raised floor systems

Tap-off Leads

l

Choose from a vast range of tap-off leads to meet installation

requirements

l

Alternative tap-offs available on request

ACCESS GROMMET

A range of 5” and 8”

grommets are available. Please

refer to page 33 for details

††

In the published 17th Edition of the IEE Wiring Regulations, these requirements are found in Regulation 543.7. (16th Edition = Section 607)

Type

Pin Position

Cable /

Conduit

Current

Rating

Protection 3 metre**

5

metre*

Key

codes

2.5

mm

2

4.0

mm

2

2.5

mm

2

4.0

mm

2

STANDARD GREY

N2 L2 PE LSF / LSF

13

A

Fused

UT31301C

UT51301C

16

mm

32

A

Unfused

UT33201

UT53201

16

mm

13

A

Fused

UT31301

UT51301

AUX / PHASE 1

GREEN

PE N1 L1

LSF / LSF

13

A

Fused

UT31302C

UT51302C

16

mm

32

A

Unfused

UT33202

UT53202

16

mm

13

A

Fused

UT31302

UT51302

PHASE 2 GREEN

PE N1

L2

LSF / LSF

13

A

Fused

UT31310C

UT51310C

16

mm

32

A

Unfused

UT33210

UT53210

16

mm

13

A

Fused

UT31310

UT51310

PHASE 3 GREEN

PE N1

L3

LSF / LSF

13

A

Fused

UT31311C

UT51311C

16

mm

32

A

Unfused

UT33211

UT53211

16

mm

13

A

Fused

UT31311

UT51311

ALL PHASE GREEN

PE N1 L1 L2 L3

16

mm

28

A

Unfused

UT33205

UT53205

CE RED

CE N1 L1

PE LSF / LSF

13

A

Fused

UT31304C

UT51304C

16

mm

32

A

Unfused

UT33204

UT53204

16

mm

13

A

Fused

UT31304

UT51304

DUO (RED)

CE N1 L1 N2 L2 PE 20mm

28

A

Unfused

UT33206

UT53206

Alternative tap-off lengths are available on request via MK Design Service, see page 7.

Tap-offs are supplied as single cables inside steel flexible conduit, except those with ‘C’ suffix, which are supplied with 3 or 4 core LSF flex, as appropriate.

*

Unfused tap-offs in excess of 3m can only be used on powertrack protected with a 32A (or less) circuit protection device.

**

When fully stretched to ensure the conductor lengths do not exceed 3m to comply with BS 7671:2008 17th Edition IEE Wiring Regulations to ensure the conduit remains

flexible this is then shortened by a further 0.1 - 0.2 of slack when wired to a module.

Add ‘

DE

suffix for Dual Earth High Integrity Earthing

††

,

e.g. UT51301

DE

.

Unfused tap-offs - High Integrity Earthing

††

as standard.

Add ‘

607

suffix for High Integrity Earthing

††

,

e.g. UT51301607.

Key codes shown are from the perspective of the Power Track socket with the keycode in the top right corner.

The tap-off key code will be a mirror image when viewed from underneath.