Table of Contents Table of Contents
Previous Page  591 / 759 Next Page
Information
Show Menu
Previous Page 591 / 759 Next Page
Page Background

Technical Hotline

+44 (0)1268 563720

CIRCUIT PROTECTION

591

RATING SPECIFICATION

DOUBLE POLE, 2 MODULE

RATING RCBO TRIPPING CURRENT

LIST NO.

16A, 110V

10mA

6016s

16A, 110V

30mA

6416s

16A, 230V

10mA

6316s

16A, 230V

30mA

5716s

32A, 110V

30mA

6032s

32A, 230V

30mAs

6730s

40A, 230V

30mA

5740s

63A, 230V

30mA

5760s

63A, 230V

100mA

6160s

63A, 230V

300mA

5860s

80A, 230V

30mA

5780s

80A, 110V

30mA

6080s

80A, 230V

300mA

5880s

80A, 230V

100mA

6180s

100A, 230V

30mA

7700s

100A, 230V

100mA

6600s

100A, 230V

300mA

7800s

DOUBLE POLE, PULSATING D.C.,

FAULT CURRENT SENSITIVE, 2 MODULE

16A, 230V

10mA

6216s

16A, 230V

30mA

6716s

32A, 230V

30mA

6630s

40A, 230V

30mA

5640s

63A, 230V

30mA

5660s

TIME DELAYED, 2 MODULE

80A, 230V

100mA

6980s

100A, 230V

100mA

6400s

FOUR POLE, 4 MODULE

25A, 230/400V

30mA

6425s

40A, 230/400V

30mA

6440s

40A, 230/400V

100mA

6240s

63A, 230/400V

30mA

6463s

63A, 230/400V

100mA

6363s

63A, 230/400V

300mA

6263s

FOUR POLE, PULSATING D.C.,

FAULT CURRENT SENSITIVE, 4 MODULE

40A, 230/400V

30mA

6640s

Installation

Sentry RCDs must never be used as the sole

method of basic protection, but are invaluable in

providing supplementary protection in high risk

environments where damage may occur.

Sentry Technical

Industrial 10kA Residual Current Devices (RCDs)

Application

The choice of the most suitable RCD for a particular application should take into

account the following considerations:

1. Sensitivity

10mA RCDs offer a high degree of protection against electrocution in an accidental

shock hazard situation. They are of particular value in a high risk area where

resistances external to the body are likely to restrict the earth fault current flowing

through the body to less than 30mA and where 110V supply is being used.

30mA RCDs offer a high degree of protection in an accidental shock hazard

situation and are by far the most popular sensitivity used in the United Kingdom. In

a shock situation, the current flowing through the human body at 240V 50Hz could

be between 80 and 240mA, depending on the resistance of the body in question.

To ensure that there are no harmful physiological effects in such a situation, it is

necessary for the RCD to operate within 300mS at 30mA and 40mS at 150mA.

As the Sentry RCD typically operates well below these times, it clearly more than

satisfies this requirement.

100mA RCDs may, in some circumstances, provide protection against electrocution

in an accidental shock hazard situation. However, it is important to note that there is

a likelihood that the earth fault current may be below the sensitivity of the RCD. This

becomes increasingly likely if additional resistances to that of the human body are in

the current path.

300mA RCDs provide protection against the risk of fire only. They do not provide

protection against electrocution in an accidental shock hazard situation. A typical

application would be lighting circuits where it is deemed that the risk of electric

shock is small.

It is important to note that a current of less than 500mA flowing in a high resistance path

is sufficient to bring metallic parts to incandescence and, potentially, initiate a fire.

2. Requirements of the IEE Wiring Regulations BS 7671

RCDs may be used to provide additional protection against both fault protection and

basic protection.

Fault Protection

Defined as protection against electric shock under single fault conditions.

Effective earthing in conjunction with automatic disconnection should always be

employed to protect against the effects of fault protection. The provision of a low

resistance path back to the supply from the fault should ensure that the overcurrent

device operates before damage occurs. This is the earth fault loop impedance.

In circumstances where the earth fault loop impedance in the circuit is too high

to ensure operation of the overcurrent device, then the IEE Wiring Regulations

allow the installation of an RCD. To comply with the Regulations, the earth loop

impedance of the circuit (in ohms), multiplied by the rated tripping current of the

RCD (in amperes) must not produce a value greater than 50. With this in mind, the

maximum values of earth loop impedance permissible when installing an MK Sentry

RCD are as follows:

50 50

Z

s

(max) = ——– = ——– = 1667 Ohms

l

n 0.03

Rated Tripping Current of RCD

Maximum Permissible Earth Fault Loop

Impedance

10mA

5000 Ohms

30mA

1667 Ohms

100mA

500 Ohms

300mA

166 Ohms

RCD’s are further specified for fault protection on TT systems (Regulation 411.5.2, 411.5.3 apply)