Switch Disconnectors

3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A

Introduction

7/78

Siemens LV 10 · 2014

7

Technical specifications

1)

Configuring note: Max. permissible operating temperature for fuse blades

135 °C, for connections 100 °C.

2)

110 V (one conducting path).

3)

220 V DC (L1 and L3 series-connected) or 110 V DC

(one conducting path) at DC-23A.

4)

At 440 V

L/R

= 4 ms, at 220 V

L/R

= 1 ms.

5)

At 440 V DC-22A, at 220 V DC-23A.

6)

3ND1 switchgear protection fuse.

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3KM50

3KM52

3KM53

3KM55

3KM57

Rated uninterrupted current

I

u

A 63

125

160

250

400

For fuse links according to DIN 43620,

(when SITOR semiconductor fuses are used, a reduction of rated

current is necessary,

see reference to technical information at start of chapter

)

Size 00 and 000 00 and 000 00 and 000 1 and 2

1 and 2

Conventional free-air thermal current

I

th

1)

A 63

125

160

250

400

Rated insulation voltage

U

i

V 690

1000

1000

1000

1000

Rated impulse withstand voltage

U

imp

kV 6

8

8

8

8

Rated operational voltage

U

e

50/60 Hz AC

V 690

DC

V 440 (3 conducting paths series-connected)

V 220 (2 conducting paths series-connected)

2)

Rated short-circuit making capacity with fuses

kA 220

220

220

176

176

(peak value, at 50/60 Hz 690 V AC)

Rated conditional short-circuit current with fuses

kA

100

100

100

80

80

At 50/60 Hz 690 V AC (rms value)

Max. rated current

I

n

of the fuses

A 80

160

160

400

400

Max. permissible power loss of the installed fuse

• NH

W 6

9

11.5

32

45

• BS

W 8 (A2/A3)

11.5 (A4)

11.5

32

45

Permissible let-through current of the fuses

kA 8

17

17

30

3)

30

3)

Maximum permissible let-through

I

2

t

value

kA

2

s 55

223

223

1000

1000

Breaking capacity

(infeed from the top or bottom)

At 400 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A 500

1000

1280

2000

3200

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

• Motor switching capacity AC-23A

kW 30

65

80

132

200

At 500 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A 500

1000

1280

2000

3200

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

• Motor switching capacity AC-23A

kW 40

90

110

185

280

At 690 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A 500

1000

1280

2000

3200

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

• Motor switching capacity AC-23A

kW 50

110

150

220

375

At 440 V DC (3 conducting paths series-connected)

4)

• Breaking current

I

c

(

L/R

= 15 ms)

A 250

500

640

1000

4)

1600

• Rated operational current

I

e

at DC-23A

A 63

125

160

250

5)

400

Rated short-time current (1 s current),

rms value

kA

2.5

3.2

3.2

8

11

Permissible ambient temperature

°C -25 ... +55 for operation

6)

°C -50 ... +80 when stored

Mechanical endurance,

operating cycles

15000

15000

15000

12000

12000

Degree of protection

IP00/IP20 (from the operator side, with fuse and terminal covers)

Power loss of the switch disconnector at

I

th

W 8.5

22

36

33

86

(plus power loss of the fuses)

Main conductor connections

Busbar systems, max. dimensions (W



T)

mm

25

9

45

10

45

10

40

12

40

15

Cable lug, max. conductor cross-section (stranded)

mm

2

35

70

120

150

2

150 or

1

240

Busbar systems, max. dimensions (W



T)

mm

25

9

45

10

45

10

40

12

40

15

Tightening torque

Nm 6 ... 7.5

7 ... 10

18 ... 22

35 ... 45

35 ... 45

Terminal screws

M6

M6

M8

M10

M10

Protective conductor connections

Flat bars

mm --

--

--

20

2.5

20

2.5

Cable lug, max. conductor cross-section (stranded)

mm

2

--

--

--

70

120