Table of Contents Table of Contents
Previous Page  5 / 158 Next Page
Information
Show Menu
Previous Page 5 / 158 Next Page
Page Background

7

Switch Disconnectors

3LD Main Control and EMERGENCY-STOP Switches up to 250 A

Introduction

7/5

Siemens LV 10 · 2014

Technical specifications

3LD main control and EMERGENCY-STOP switches for UL/CSA

1)

Depending on the cable infeed, only small cross-sections are possible with

devices in molded-plastic enclosures

2)

Values in brackets apply to devices in molded-plastic enclosure

Standards

DIN VDE 0660, IEC 60947

Switches

Type

3LD20 3LD21 3LD22 3LD25 3LD27 3LD28 3LD23 3LD24

Rated insulation voltage

U

i

V 690

690

50 ... 60

Rated operational voltage

U

e

V AC

Rated frequency

Hz

Rated impulse withstand voltage

U

imp

kV 6

6

6

6

6

6

6

6

Rated short-time withstand current

(1 s current, rms value)

A 340

640

640

1260

2000 2000 4000 4000

Short-circuit protection, max. back-up fuse (gL)

A 20

25

40

63

100

125

160

250

Rated conditional short-circuit current with upstream fuses

at AC 50/60 Hz, 690 V

kArm

s

50

50

50

50

50

20

50

50

Maximum permissible let-through

I

2

t

value

kA

2

s 2.5

4

9

21

64

104

185

557

Permissible let-through current of the fuse

kA 3

3.5

4.5

6

10

10

15

15

Rated uninterrupted current

I

u

A 16

25

32

63

100

125

160

250

AC-21A load-break switch

Rated operational current

I

e

A 16

25

32

63

100

125

160

250

AC-3 motor load switches

In-service switching

of individual motors

Rating

At 220 ... 240 V

At 380 ... 440 V

At 660/690 V

kW

kW

kW

3.0

5.5

5.5

4.0

7.5

7.5

5.5

9.5

9.5

11.0

18.5

15.0

18.5

30.0

22.0

22.0

37.0

30.0

35.0

50.0

37.0

55.0

110.0

45.0

AC-23A main control switch

Repair switch

frequent, but not in-service switching

of individual motors

Rating

At 220 ... 240 V

At 380 ... 440 V

At 660/690 V

kW

kW

kW

4.0

7.5

7.5

5.0

9.5

9.5

6.0

11.5

11.5

11.0

22.0

18.5

18.5

37.0

30.0

22.0

45.0

37.0

45.0

75.0

45.0

75.0

132.0

55.0

Power loss per conducting path

at

I

e

W 0.5

1.1

1.8

4.5

7.5

12.0 36.0 36.0

Endurance

mechanical

Switching cycles

100 000

Switching frequency

1/h 50

Permissible ambient temperature

°C -25 ... +55

Isolating features

Up to max.

V 690

Conductor cross-sections for main conductors

1)

Solid or stranded

mm

2

1 ... 6 1.5 ... 16 1.5 ... 16 2.5 ... 35 4 ... 50 4 ... 50 16 ...185 16 ... 185

Finely stranded with end sleeve (max.)

mm

2

4

10

10

16

35

35

150

150

Conductor cross-sections

Copper cable

AWG 18 ... 10 14 ... 8 14 ... 8 14 ... 6 12 ... 1 12 ... 1

Torque for terminal

Nm 1.5 ... 2 2 ... 2.5 2 ... 2.5 2.5 ... 3 2.5 ... 3 2.5 ... 3 9.5 ... 10 9.5 ... 10

Touch protection

according to EN 50274

Yes

Auxiliary switches

Rated insulation voltage

U

i

V 500

Rated operational voltage

U

e

V AC 500

Rated uninterrupted current

I

u

A 10

Rated operational current

I

e

, AC-15 At 120 V

A 6

At 220 ... 240 V

A 3

At 380 ... 415 V

A 1.8

At 500 V

A 1.4

Short-circuit protection, aux. switch,

max. back-up fuse (gL/gG)

A 10

Conductor cross-sections for auxiliary conductors

Connection type

Terminals

2 × (0.75 ... 2.5), 1 × 4

2 × (0.75 ... 1.5) 1 x 2.5

0.8

Solid or stranded

mm

2

Finely stranded with end sleeve

mm

2

Torque for terminal

Nm

Standards

UL/CSA

Switches

Type

3LD20 3LD21 3LD22 3LD25 3LD27 3LD28 3LD23 3LD24

Rated operational voltage

U

e

V AC 600

600

600

600

600

600

600

600

Rated uninterrupted current

I

u

A 10

20

30

60

100

125

160

250

Current rating

A 600 A 600 A 600 --

--

--

--

--

Pilot duty

P 600 P 600 P 600 --

--

--

--

--

Conventional thermal current

I

th

A 16

25

32

63

100

125

160

250

Maximum rated power (AC-3)

3



120 V

HP 1

3

3

5

10

15

--

--

Alternating current motors 40 ... 60 Hz

240 V

HP 3

7.5

10 (7.5)

2)

15

30

40

40

50

(HP = PS)

480 V

HP 7.5

10

20 (15)

2)

40

60

75

75

100

600 V

HP 10

15

30 (20)

2)

50

75

100

75

75

1



120 V

HP 0.5

2

2

3

--

--

--

--

240 V

HP 1.5

3

3

10

--

--

--

--

Conductor cross-sections

Cu cable

AWG 18 ... 10 14 ... 8 14 ... 8 14 ... 6 12 ... 1 12 ... 1 1 ... MCM400

Torque

Nm 1.5 ... 2 2 ... 2.5 2 ... 2.5 2.5 ... 3 2.5 ... 3 2.5 ... 3 10

10

© Siemens AG 2014