Switch Disconnectors

3KA, 3KE Switch Disconnectors up to 1000 A

Introduction

7/34

Siemens LV 10 · 2014

7

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3KE42

3KE43

3KE44

3KE45

Rated uninterrupted current

I

u

A 250

400

630

1000

Rated insulation voltage

U

i

V 1000 AC, 1200 DC

Rated impulse withstand voltage

U

imp

kV 8

8

8

8

Rated operational voltage

U

e

50/60 Hz AC

V 690

DC

V 440 (3 conducting paths series-connected)

V 220 (2 conducting paths series-connected)

Rated short-circuit making capacity

I

cm

kA

35

35

60

60

At 50/60 Hz 690 V AC, peak value

Rated short-circuit making capacity with upstream fuses

kA

105

105

105

84

At 50/60 Hz 690 V AC, peak value

Rated conditional short-circuit current

with upstream fuses

A 50

50

50

40

At 50/60 Hz 690 V AC (rms value)

Maximum permissible let-through

I

2

t

value

kA

2

s 2150

2150

5400

19000

Permissible let-through current of an upstream circuit

breaker

At 50/60 Hz 690 V AC, peak value

kA

35

35

60

60

Max. rated current

I

n

of the fuse

A 400

400

630

1000

Permissible let-through current of the fuses (peak value)

kA

38

38

60

75

Breaking capacity

(infeed from the top or bottom)

At 400 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A

1000

1000

2520

2520

• Rated operational current

I

e

at

- AC-21A

A 250

400

630

1000

- AC-22A

A 250

330

630

800

- AC-23A

A 125

125

315

315

At 500 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A

1000

1000

2520

2520

• Rated operational current

I

e

at

- AC-21A

A 250

400

630

1000

- AC-22A

A 250

330

630

800

- AC-23A

A 125

125

315

315

At 690 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A

1 000

1000

2520

2520

• Rated operational current

I

e

at

- AC-21A

A 250

400

630

1000

- AC-22A

A 250

330

630

800

- AC-23A

A 125

125

315

315

At 440 V DC (3 conducting paths series-connected)

• Breaking current

I

c

(

L/R

= 5 ms)

A 1000

1000

2520

2520

• Rated operational current

I

e

at

- DC-21A

A 250

400

630

1000

- DC-22A

A 250

250

630

630

Rated short-time current

I

cw

(1 s current, rms value)

kA

12.5

12.5

21

21

Permissible ambient temperature

°C -25 ... +55 for operation

°C -50 ... +80 when stored

Mechanical endurance,

operating cycles

10 000

Degree of protection

IP00

Power loss of the switch disconnector at

I

th

W 15

33

78

180

Main conductor connections

Busbar systems, max. dimensions (W x T)

mm 25 x 10

25 x 10

2 x 40 x 10

2 x 40 x 10

Cable lug, max. conductor cross-section (stranded)

mm

2

2 x 150

2 x 150, 1 x 240

2 x 240

2 x 240

© Siemens AG 2014