18/36 IZM circuit-breakers, IN switch-disconnectors
Accessories for IZMX16
2010 CA08103002Z-EN
www.eaton.comAccessories for IZMX16
Auxiliary contacts
Overload trip
IZMX-AS22
IZMX-OTS
IZMX-LCS16(-SR)
Rated breaking
capacity
Inductive load
250 V AC
A 10
10
10
125 V DC
A 0.5
0.5
0.5
250 V DC
A 0.25
0.25
0.25
Voltage releases
Closing releases
IZMX-
ST24DC
IZMX-
STS24DC
IZMX-
ST48DC
IZMX-
STS48DC
IZMX-
ST110AD
IZMX-
STS110AD
IZMX-
ST230AD
IZMX-
STS230AD
IZMX-
SR24DC
IZMX-
SR48DC
IZMX-
SR110AD
IZMX-
SR230AD
Rated control
voltage
AC 50/60 Hz
U
s
V –
–
110 - 127 208 - 240 –
–
110 - 127 208 - 240
DC
U
s
V 24
48
110 - 125 220 - 250 24
48
110 - 125 220 - 250
Power consumption
AC
VA –
–
(pick-up
450)
(pick-up
450)
–
–
(pick-up
450)
(pick-up
450)
DC
W (pick-up
250)
(pick-up
250)
(pick-up
450)
(pick-up
450)
(pick-up
250)
(pick-up
250)
(pick-up
450)
(pick-up
450)
Response time of
the circuit-breaker
with U
s
ms 35
35
35
35
40
40
40
40
Operating range
Drop-out voltage
AC operated,
50/60 Hz
Drop-
out
x U
c
–
–
–
–
–
–
–
–
Pick-up voltage
pick-
up
x U
c
Acc.toIEC
standard
Acc. toIEC
standard
Acc. to IEC
standard
Acc. to IEC
standard
Acc.toIEC
standard
Acc.toIEC
standard
Acc.toIEC
standard
Acc. toIEC
standard
Under-voltage releases
IZMX-UVR24DC
IZMX-UVR48DC
IZMX-UVR110AD
IZMX-UVR220AD
Rated control
voltage
AC 50/60 Hz
U
s
V –
–
110 - 127
208 - 240
DC
U
s
V 24
48
110 - 125
220 - 250
Power consumption
AC
VA –
–
5 (pick-up 890)
5 (pick-up 910)
DC
W 5 (pick-up 500)
5 (pick-up 850)
5 (pick-up 890)
5 (pick-up 910)
Response time of
the circuit-breaker
with U
s
ms 50
50
50
50
Operating range
Drop-out voltage
AC operated,
50/60 Hz
Drop-
out
x U
c
Acc. to IEC standard
Acc. to IEC standard
Acc. to IEC standard
Acc. to IEC standard
Pick-up voltage
pick-
up
x U
c
Acc. to IEC standard
Acc. to IEC standard
Acc. to IEC standard
Acc. to IEC standard
IZMX-AS22, IZMX-OTS, IZMX-S..., IZMX-U...