Background Image
Table of Contents Table of Contents
Previous Page  225 / 439 Next Page
Information
Show Menu
Previous Page 225 / 439 Next Page
Page Background

Motor-protective circuit-breakers PKZM01, PKZM0, PKZM4, PKE

Switching capacity

2010

CA08103002Z-EN

www.eaton.com

7/33

Circuit-breaker switching capacity

Rated uninterrupted current I

u

Rated conditional short-circuit current I

q

IEC/EN 60947-4-1

Rated maximum short-circuit breaking capacity I

cu

IEC/EN 60947‐2

Rated breaking capacity I

cs

}

230

V

400

V

440

V

2)

500

V

2)

690

V

2)

I

u

I

q

I

cu

I

cs

I

q

I

cu

I

cs

I

q

I

cu

I

cs

I

q

I

cu

I

cs

I

q

I

cu

I

cs

A

kA kA kA A

1)

kA kA kA A

1)

kA kA kA A

1)

kA kA kA A

1)

kA kA kA A

1)

PKZM01 with type “1” and “2” coordination

0.16 – 1

50 50 50 50

50 50 50 50

50 50 50 50

1.6

50 50 50 50

50 50 50 50

50 50 50 50

2.5

50 50 50 50

50 50 50 50

50 50 50 50

4

50 50 50 50

50 50 50 50

50 50 50 50

6.3

50 50 50 50

50 50 50 50

50 50 50 50

10

50 50 50 50

50 50 50 50

42 42 10 50

12

50 50 10 50

50 50 10 50

15 15 10 50

16

50 50 10 50

50 50 10 50

15 15 10 50

20, 25

50 50 10 50

50 50 10 50

10 10 3 50

PKZM4 with type “1” and “2” coordination

16

150 150 25

N 150 150 25 N 45 45 25 100 15 15

100 8 8 2.5 100

25

150 150 25

N 150 150 25 N 45 45 25 100 15 15

100 8 8 2.5 100

32

50 50 25 100 50 50 25 100 45 45 25 100 15 15

100 5 5 2.5 100

40

50 50 25 100 50 50 25 100 45 45 25 100 15 15

100 5 5 2.5 100

50

50 50 25 100 50 50 25 100 45 45 25 100 15 15

100 5 5 2.5 100

58

50 50 25 160 50 50 25 160 45 45 25 160 15 15

160 5 5 2.5 160

63

50 50 25 160 50 50 25 160 45 45 25 160 15 15

160 5 5 2.5 160

PKE12...

2)

with type of coordination „1“ and

0.3 - 1.2

100

50

100

50

50

50

10

50

3

50

1 - 4

100

50

100

50

50

50

10

50

3

50

3 - 12

100

50

100

50

15

50

10

50

3

50

PKE32...

2)

with type of coordination „1“ and

3 - 12

100

50

100

50

15

50

6

50

3

50

8 - 32

100

50

100

50

25

50

6

50

3

50

Notes

No upstream protective device

required,as it is the auto-

protected range (150 kA)

1)

Fuse (A gG/gL) for increasing the switching capacity of the motor-protective

circuit-breaker to 100 kA

2)

Please enquire for additional information regarding voltages >400 V and

device combinations with CL-PKZ0.

N Not necessary

PKZM01, PKZM4, PKE

Motor-protective circuit-breaker internal resistances

Impedance

Heat

dissipation

(3

pole at

operating

temperature)

Rated

uninterrupted

current I

u

Ω

W

A

PKZM0-0,16

78

6

0.16

PKZM0-0.25

32

6

0.25

PKZM0-0.4

13

6

0.4

PKZM0-0.63

5

6

0.63

PKZM0-1

2

6

1

PKZM0-1.6

0.8

6

1.6

PKZM0-2.5

0.32

6

2.5

PKZM0-4

0.13

6

4

PKZM0-6.3

0.050

6

6.3

PKZM0-10

0.020

6

10

PKZM0-12

0.014

6

12

PKZM0-16

0.008

6

16

PKZM0-20

0.005

6

20

PKZM0-25

0.003

6

25

PKZM0-32

0.002

6

32

Impedance

Heat

dissipation

(3

pole at

operating

temperature)

Rated

uninterrupted

current I

u

Ω

W

A

PKZM4-16

0.029

22

16

PKZM4-25

0.012

22

25

PKZM4-32

0.007

22

32

PKZM4-40

0.005

22

40

PKZM4-50

0.003

22

50

PKZM4-58

0.002

22

58

PKZM4-63

0.002

22

65

PKZ2-ZM-0.6

13

14

0.6

PKZ2-ZM-1

5

14

1

PKZ2-ZM-1.6

2

14

1.6

PKZ2-ZM-2.4

0.8

14

2.4

PKZ2-ZM-4

0.29

14

4

PKZ2-ZM-6

0.13

14

6

PKZ2-ZM-10

0.05

14

10

PKZ2-ZM-16

0.018

14

16

PKZ2-ZM-25

0.007

14

25

PKZ2-ZM-32

0.005

14

32

PKZ2-ZM-40

0.003

14

40