154
WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION
PG00400018U – March 2012
Contactors type CR, lamp load table
(continued)
Lighting
Lamp load (Watt)
Maximum number of fittings per contactor type
Type
CR 20
CR 25
CR 40
CR 63
Low pressure sodium vapour lamp
Uncompensated
18
22
27
71
90
35
7
9
23
30
55
7
9
23
30
90
4
5
14
19
135
3
4
10
13
180
3
4
10
13
Parallel compensated
18
6
7
44
66
35
1
1
11
16
55
1
1
11
16
90
1
1
8
12
135
-
-
4
7
180
-
-
4
7
High pressure sodium vapour lamp
Uncompensated
150
5
6
17
22
250
3
4
10
13
400
2
2
6
8
1000
-
1
3
3
Parallel compensated
150
1
1
11
16
250
-
1
6
10
400
-
-
4
6
1000
-
-
2
3
General remarks:
1) In case a 4-pole contactor is used (3 ph. + neutral) the above mentioned quantity of lamps need to be multiplied by 1,5 to obtain the maximum quantity of fittings for the contactor. The total
quantity of fitting need to be split equally across the 3 poles.
2) In case multiple contactors are installed in one panel it is required to multiply the above mentioned fittings by the applicable load factor according the IEC 60439-1.
3) It is recommended to install one spacer between each 2 contactors installed (eg contactor, contactor, spacer, contactor, etc.)