WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

Contactors type CR, lamp load table

(continued)

Lighting

Lamp load (Watt)

Maximum number of fittings per contactor type

Type

CR 20

CR 25

CR 40

CR 63

Low pressure sodium vapour lamp

Uncompensated

18

22

27

71

90

35

7

9

23

30

55

7

9

23

30

90

4

5

14

19

135

3

4

10

13

180

3

4

10

13

Parallel compensated

18

6

7

44

66

35

1

1

11

16

55

1

1

11

16

90

1

1

8

12

135

-

-

4

7

180

-

-

4

7

High pressure sodium vapour lamp

Uncompensated

150

5

6

17

22

250

3

4

10

13

400

2

2

6

8

1000

-

1

3

3

Parallel compensated

150

1

1

11

16

250

-

1

6

10

400

-

-

4

6

1000

-

-

2

3

General remarks:

1) In case a 4-pole contactor is used (3 ph. + neutral) the above mentioned quantity of lamps need to be multiplied by 1,5 to obtain the maximum quantity of fittings for the contactor. The total

quantity of fitting need to be split equally across the 3 poles.

2) In case multiple contactors are installed in one panel it is required to multiply the above mentioned fittings by the applicable load factor according the IEC 60439-1.

3) It is recommended to install one spacer between each 2 contactors installed (eg contactor, contactor, spacer, contactor, etc.)

Technical data

Control and switching devices dimensions and data

12.6